INSTRUCTIONS FOR INSTALLATION AND USE
EN
T120-T240
Should errors
F, G, h, I
or
J
occur, the automation will automatically perform the sensors resetting operation.
If the first resetting operation is positive, the automation will start working properly again though storing the error in
the error history file.
Should the first reset fail, the automation will make an attempt every 30 sec for max 24 hours. If the error is not
solved within 24 hours, the automation will eventually stop working and the intervention of a professional will become
necessary.
SELF RESTORE MANAGEMENT OF ERRORS F-G-h-I-J
Only on the model with antipanic wing, after the wings have been forced open, the automation stops and the
wings have to be refastened manually. After refastening the wings, the automation will remain blocked for 20
second, then will perform a reset (near).
If the doors are smashed until the automation mode is closed and subsequently repositioned does not run no
movement reset.
For full antipanic systems (forcing of both mobile and semifixed wings) it is possible to install a microswitch kit
instead of the photocells, to block the automation in case of forcing of the wings.
For proper operation of the automated system with panic mounted photocells TOPP.
SELF RESTORE MANAGEMENT AFTER ANTI PANIC ALARM
5.9
5.10
The opening of emergency or fire causes the immediate opening of the automation, but in case where the sensors
side are occupied. As long as the contact remains active automation remains open, once the contact is deactivated
automation will return to the operation previously set by digital switch DS2 or analog selector Ms1.
The emergency opening or opening fire is manageable via a control unit or an emergency button connected to the
card .The setting of the logic of contact on the card type is NO (normally open). The logic of contact it can be varied
only by the digital switch DS2 in the PARAMETERS MENÙ -> PAR. VARIOUS -> LOGIC EMER. for the logic of
emergency contact and PARAMETERS -> PAR. VARIOUS -> LOGIC ANTINC. for logic fire.
SELF RESTORE MANAGEMENT AFTER OPENING FIRE OR AN OPENING OF EMERGENCY
5.11
Once freed sensors the reset (near) resumes automatically. Throughout the zeroing phase (near) the automation will
move at a reduced speed.
If there is one of the errors mentioned above as long as it is set to the "CLOSED" by DS2 digital or analog selector
switch MS1, automation will not perform any reset (near) as long as this mode will not be changed, or if it will request
the opening of impulse key or emergency opening / fire. Once changed how automation will perform the reset (near)
as shown above.