2.5 EMC Wiring Guidelines
Shielding and grounding
Tolomatic supplied cables have the proper shielding and are recommended for proper installation. If additional or
alternate cables are require, braided shield cables are recommended. The standard cables provided by Tolomatic
have an overall braided shield. To minimize EMI and ensure system reliability, all shield drain wires from all cables
should be tied to a common earth ground. Also, make sure to follow the drive manufacturer’s recommendations on
proper cable dressing, shield and ground connections to ensure reliable operations. To minimize EMI and ensure
system reliability, shield drain wires from all cables should be tied to a common earth ground.
Thrust rod is not electrically connected to ground. The thrust rod should be earth grounded during installation for
safety when possible.
2.6 Motion Control System Selection Recommendations
It is recommended that all servo drives be selected based on the following important parameters:
a) CE and UL approved system
b) Thermal switch input
c) Servo drive sizing key parameters for IMA-S
i) Peak current
ii) Voltage
iii) Peak RPM
iv) Max current switching frequency
2.7 Identification Label
Figure 2.2: Tolomatic IMA Actuator identification label.
Do not remove the identification label. Do not render it unreadable.