38
10. Table of identifiers (codes)
For the setting range, options, initial values, and similar parameters, see the operation manual for
this system.
Note: 1. The R/W to characters that do not meet the display conditions responds with "NAK2."
2.
□
in the identifier table indicates a space (ASCII code:20H).
3. L/B is not applicable during MODBUS communications. (L/B is usable only with
TOHO communications.)
Run mode
toho
modbus
Screen
character
Name
Command Remark
Identifier
Absolute
(DEC)
Relative (hex)
PV1
40001
0000
Measuring temperature
RLB
HHHHH: Overscale
LLLLL: Underscale
At L/B
00000: Displays PV alone
00001: Displays SV alone
00002: Displays PV/SV
STS
40003
0002
Step SV screen
RWLB
STM
40005
0004
Step time monitor
RWLB
PRM
40007
0006
Operating screen
Run operation
W
LB
00000: Run stop
00001: Run start
00002: Run pause
00003: Run restart
00004: Step feed
Run status monitor
R
00000: Before a run
00001: In WAIT (in ramp)
00002: In a run
00003: Pause
00004: Run end
* Regarding the operating screen (PRM): Meanings of the same numerical data is different for between
reading and writing.