18
6.3 Composition of an RTU request message (transmitted from a high-level
computer to this product)
For codes a) through i), see "6.5 Description of RTU codes."
6.3.1 Composition of a read request message
a) Slave address
01H
b) Function code
03H
c) Register address
High level
00H
First register address
Low level
00H
d) Number of registers
High level
00H
Fixed at 2
Low level
02H
e) CRC-16
Low level
0BH
High level
C4H
6.3.2 Composition of a write request message
a) Slave address
01H
b) Function code
10H
c) Register address
High level
00H
First register address
Low level
00H
d) Number of registers
High level
00H
Fixed at 2
Low level
02H
f)
Number of byte items
04H
Number of registers
2
g)
Data for the first register
(a low-level word)
High level
00H
③
Data composition is
①
,
②
,
③
,
and
④
H. (
①
represents 1
byte.)
Low level
00H
④
Data for the first register
(a high-level word)
High level
00H
①
Low level
00H
②
e) CRC-16
Low level
3FH
High level
FEH
6.3.3 Composition of a store request message
a) Slave address
01H
b) Function code
10H
c) Register address
High level
02H
First register address
Low level
0EH
d) Number of registers
High level
00H
Fixed at 2
Low level
02H
f)
Number of byte items
04H
Number of registers
2
g)
Data for the first register
(a low-level word)
High level
00H
The data about the storage of settings
is arbitrary.
Low level
00H
Data for the first register
(a high-level word)
High level
00H
Low level
00H
e) CRC-16
Low level
E2H
High level
EBH