Communication manual TOHO ELECTRONICS INC.
DWG.No. 4B-6829-A
- 45 -
6.19.
Comm. Settings
TOHO
MODBUS
Name
Command
Remark
First
Identifier
Second
Identifier
Absolute
(DEC)
Relative
(hex)
PRT
44865
1300
Protocol
RW
0
:
TOHO
1
:
MODBUS
MFO
44867
1302
Format
RW
0
:
Type 1/RTU
1
:
Type 2/ASCII
ADR
44869
1304
Comm. Address
RW
BPS
44871
1306
Comm. Speed
RW
0
:
2400bps
1
:
4800bps
2
:
9600bps
3
:
19200bps
4
:
38400bps
DAT
44873
1308
Data Length
RW
0
:
7bit
1
:
8bit
STB
44875
130A
Stop bit
RW
0
:
1bit
1
:
2bit
PAL
44877
130C
Parity check
RW
0
:
OFF
1
:
EVEN
2
:
ODD
BCC
44879
130E
BCC check
RW
0
:
OFF
1
:
ON
AWT
44881
1310
Resp delay
RW
6.20.
Clock
TOHO
MODBUS
Name
Command
Remark
First
Identifier
Second
Identifier
Absolute
(DEC)
Relative
(hex)
TYE
44353
1100
Year
RW
TMO
44355
1102
Month
RW
TDA
44357
1104
Day
RW
THO
44359
1106
Hour
RW
TMI
44361
1108
Minute
RW
TSE
44363
110A
Second
RW
6.21.
Language
TOHO
MODBUS
Name
Command
Remark
First
Identifier
Second
Identifier
Absolute
(DEC)
Relative
(hex)
LNG
40027
001A
Language
RW
0
:
English
1
:
Japanese