EN 54-16
Figure 4: Label for cabinets
7. STANDBY (RESERVE, REDUNDANT) AMPLIFIERS
The standby amplifier's output power must be the same or more than that of the amplifier with the highest output
power to be replaced in case of an amplifier fault.
8. SETTING ON THE SYSTEM MANAGER SX-2000SM
To comply with EN 54-16, set the fault reset button on the system manager SX-2000SM into the special mode.
Protective cover
Screw
Inside of the protective cover
DIP switch
ON
1 2 3 4 5 6 7 8
To do so, open the protective cover, set DIP switch no. 4 to "ON."
Replace the protective cover and fix it by the screw.
For the operation of the fault reset button, please refer to chapter 3.1.
6. CABINETS
The cabinet racks of the CR-series, namely the CR-15, CR-22, CR-27, CR-35, CR-40 and CR-44, shall be used
for installing the system components.
Each cabinet rack containing this certified SX-2000 equipment must be labelled with the label shown below.
This label will be supplied as accessory with each SX-2000SM and SX-2100AO.
The same label will be provided for the remote microphones. When you install them inside a (lockable) box, put
the label onto this box.
The label must be affixed so that it can be seen in access level 1.