167
• Accessories
Removable terminal plug (8 pins) ............................................. 4
Removable terminal plug (6 pins) ............................................. 8
Removable terminal plug (4 pins) ............................................. 1
Removable terminal plug (2 pins) ............................................. 1
Rack mounting screw with plain washer (5 x 12) ..................... 4
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
DS Link
Usable unit
VX-2000DS, VX-3000DS
Connector/Cable
2 interfaces, RJ45 Connector,
Shielded Category 5 twisted pair cable for LAN (CAT5-STP)
Maximum Cable Distance
5 m
CI/CO Link
Usable unit
SX-2000CI or SX-2000CO
Connector/Cable
1 interface, RJ45 Connector,
Shielded Category 5 twisted pair cable for LAN (CAT5-STP)
Maximum Cable Distance
800 m
Speaker Line Failure Detection Section
Connector/Cable
Removable terminal blocks, SP/AMP: 8 pins per terminal block,
STANDBY AMP: 2 pins, AWG 16 – 24
Maximum Input Voltage
and Current
100 Vrms, 5 Arms
Fault Detection System
Short circuit, open circuit, ground fault
Method
Impedance or End of line
End of line
In Case of Normal: Terminated by 470 kΩ between the speaker line and
the shield
In Case of Open: Opened between the speaker line and the shield
Impedance
Minimum Load: 2 kΩ (5 W) at 100 V line
Control Input
8 inputs, no-voltage make contact input, open voltage: Under 40 V DC,
short-circuit current: 2 mA, photo coupler input,
removable terminal block (6 pins)
Control Output
8 outputs, C contact, no-voltage make contact output: relay contact output
(withstand voltage: 40 V DC, control current: 2 – 300 mA),
removable terminal block (6 pins)
Operating Temperature
0°C to 40°C
Operating Humidity
35% to 80% RH (no condensation)
Finish
Panel:
Aluminum, black, alumite
Case:
Surface-treated steel plate
Dimensions
482 (w) x 88.4 (h) x 349 (d) mm
Weight
7.1 kg