General Description
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Application
The PowerTrap is used to discharge liquid from vacuum-pressure or low-pressure areas
to high-pressure areas, or from lower to higher elevations.
There are two types of delivery systems (piping methods): the closed system and the
open system. The GP10F is for use with open systems. It can be used with closed
systems, but only where there is
always
a
negative
pressure differential (e.g. vacuum
equipment). Other PowerTrap models are available for different systems.
Check to make sure which PowerTrap model is most suitable for use on the type of
system that is being planned for installation.
Type of
System
Closed System
Open System
System
Overview
Equip-
ment
Reservoir
Condensate
Recovery Line
Exhaust
Pipe
Power
Trap
Equip-
ment
Reservoir
Power
Trap
Equip-
ment
Steam
Trap
Steam
Trap
Power
Trap
Equip-
ment
Receiver
Discharge to
Atmosphere
Condensate
Recovery line
Venting
Pipe
Exhaust
Pipe
Overflow Pipe
Equip-
ment
Steam
Trap
Steam
Trap
Power
Trap
Equip-
ment
Receiver
Discharge to
Atmosphere
Condensate
Recovery line
Venting
Pipe
Exhaust
Pipe
Overflow Pipe
Benefits
No need for external steam trap (GT
model features built-in trap)
No flash steam discharge
Small reservoir
Use with vacuum equipment possible
Collection of condensate from multiple
equipment possible
Can be used where trap is lower than
receiver, such as equipment situated
near grade (providing there is sufficient
differential pressure)
Notes
Only one piece of equipment possible
per system
Equipment has minimum height
requirement to ensure that condensate
flows naturally, by gravity
(approx.: GP14/GT14/GP10/GP10/
GT10 – 0.8 m (32 in); GP10F – 1 m
(40 in); GP10L/GT10L – 0.3 or 0.5 m
(12 or 20 in); GT5C – 170 mm (7 in))
Separate steam trap required for each
piece of equipment
Requires venting pipe to discharge
flash steam to atmosphere
Model
Mechanical pump with built-in trap
GT14/GT10/GT10L/GT14L/GT14M/
GT5C
Mechanical pump
GP14/GP10/GP10L/GP14L/GP14M/
GP5C/GP10F
Where there is
ALWAYS
a
negative
pressure differential
(e.g. vacuum equipment),
GP14/GP10/GP10L/GP14L/GP14M/
GP5C/GP10F
can be used