172-65378MA-03 (GP10F PowerTrap) 23 Apr 2019
15
(2) When flash steam is not involved
(For closed systems)
Determining the reservoir diameter and length
based on the amount of condensate:
Reservoir Table
(For equalized, closed system installations)
Amount of
Pumped
Medium
Reservoir Diameter (mm) & Length (m)
Amount of
Pumped
Medium
Reservoir Diameter (in) & Length (ft)
(kg/h)
40
50
80 100 150 200 250
(lb/h)
1½
2
3
4
6
8
10
300 or less 1.2m 0.7
500 or less 3.0 ft 2.0
400
1.5 1.0
700
4.0 2.5 1.0
500
2.0 1.2 0.5
1000
5.5 3.5 1.5
600
1.5 0.6
1200
4.5 2.0 1.0
800
2.0 0.8 0.5
1500
2.5 1.5
1000
1.0 0.7
2000
3.5 2.0
1500
1.5 1.0
3000
4.5 3.0
2000
2.0 1.3 0.6
4000
6.5 4.0 1.5
3000
2.0 0.9 0.5
5000
5.0 2.5
4000
1.2 0.7
6000
5.5 2.5 1.5
5000
1.4 0.8 0.5
7000
6.5 3.0 1.5
6000
1.7 1.0 0.6
8000
3.5 2.0
7000
2.0 1.2 0.7
9000
4.0 2.5
1.5
8000
1.3 0.8
10000
4.5 2.5
1.5
9000
1.5 0.9
12000
5.0 3.0
2.0
10000
1.7 1.0
14000
6.0 3.5
2.5
16000
6.5 4.0
2.5
18000
4.5
3.0
20000
1.5
1.5
NOTE: Reservoir length can be reduced by 50% when the motive pressure (Pm) divided by the
back pressure (P
b
) is "2" or greater. (When Pm ÷ P
b
≥
2)
(3)
When there are small quantities of flash steam and a large amount of condensate
(e.g., open systems pumping large amounts of super-cooled condensate)
Consult the sizing tables in sections (1) and (2) above.
Select the condensate receiver size based on the larger of (1) and (2).
Select the vent pipe diameter and overflow pipe diameter from (1).
Reservoir
P
1
Condensate
PowerTrap