172-65441A-04 (JL14-X/JLH14-X/JLH14-B) 20 Jan 2021
16
Problem
Diagnosis (Cause)
Remedy
Steam is
discharged or
leaks from the
trap outlet
(blowing)
(steam leakage)
Check sliding sections of lever unit:
- Is rust and/or scale obstructing movement of the
lever unit?
- Is the movement of the lever smooth?
Clean or replace with a
new lever unit
Check the air vent:
- Check for damage to or rust and scale on the X-
element or the bimetal
Replace parts where
necessary
Check for proper installation
Install correctly
Check for trap vibration
Lengthen the inlet
piping and fasten it
securely
Steam is
leaking from a
place other than
the outlet
Check for gasket deterioration or damage
Replace with new
gasket(s)
Check to make sure that the proper tightening
torques were used
Tighten to the proper
torque
Erosion has occurred in the body or cover
Replace with a new
product
Float frequently
becomes
damaged
Check to see if water hammer has occurred
Study and correct the
piping