11. J3S-X S1 / J3S-X S2
•
Configuration
•
Built-in Screen
- J3S-X S1: without wire mesh
- J3S-X S2: with wire mesh
•
Countermeasures for Steam Locking
A lock release valve (model: LR3) can be added afterwards. The S series has a plug in
the cover that can be removed to allow an LR3 lock release valve to be installed to
alleviate this problem.
For details, refer to chapter 10
•
X-element
A special H-type X-element is used for the S series (a B-type X-element is equipped
on the Standard J3S-X). This X-element is for venting air not only at batch run startup,
but also during operation, preventing temperature drops. In addition, it ensures secure
sealing.
•
Installation of the Blowdown Piping
A drain plug at the bottom of the body is equipped as standard. By removing the plug
and installing an automatic or manual valve, condensate blowdown can be carried out
when the steam-using equipment experiences a temperature drop.
Part
Torque
Distance
Across Flats
Cover Plug
Drain Plug
N·m (lbf·ft)
30 (22)
35 (26)
mm (in)
19 ( )
21 ( )
4
3
/
16
13
/
Drain Plug
Cover Plug
Screen
Special X-element
for J3S-X S-series
S1: without wire mesh
Screen
(with Float Cover)
S2: with wire mesh
Plug
Lock Release Valve
(LR3)
Drain Plug (G(PF) )
A thread conversion fitting
(including the gasket)
is needed for piping.
1
/
4
̶ 14 ̶
English
Summary of Contents for J3S-X
Page 33: ...4 37 17 2 8 11 3 8 21 1 7 6 5 4 16 9 12 X 15 13 X 14 J3S X J5S X J6S X...
Page 34: ...5 1 2 3 4 5 800mm 6 7 8 6 1 2 3 4 5 6 T 25 50mm 5 5 5 5 33...
Page 36: ...A B C X 12 8 11 8 21 3 4 5 6 7 X C TLV 1 2 3 4 5 6 7 8 3 5 6 4 1 X X J3S X J5S X J6S X 35...
Page 37: ...36 9 5 6 31 8 TLV TrapMan TLV Pocket TrapMan TLV TrapMan X X X X...