26
7.2.2.1
Connecting the card reader
7.2.2.2
Wiring requirements
The wiring required between the card reader and the Orion is listed below:
Cable
Communication
protocol
Remote
Communication between
UTP ≥Cat5e
Wiegand
120m
Orion and Sirius i-series card reader
Clock/Data
50m
7.3
Bus configuration with card reader
If an Orion is connected in bus configuration (kpBus):
•
communication must be established via the black 4-pole screw connector
•
a maximum of eight Orions per kpBus applies
•
the maximum cable length is 600m
•
the power feed does not run across the kpBus
•
every Orion must be provided with its own power feed
•
the serial number and location of every Orion must be noted (see section 2.1)
Orion reader &
IO-1/2
Sirius i-serie
Description
Wire color
Sticker
Description
D0
White/orange
3
D0
-
Orange
-
-
D1
White/green
4
D1
+V
Blue
Vcc
Vcc
LED
White/blue
5
LED
-
Green
-
-
C
White/brown
GND
GND
C
Brown
GND
GND
Summary of Contents for KEYPROCESSOR Orion
Page 1: ...1 Pluto Orion Doc no 01052018 Modular controller line Installation instructions ...
Page 4: ...4 ...
Page 58: ...58 14 2 72000206 Pluto Orion with Sirius RS485 and IO ...
Page 59: ...59 14 3 72000202 Pluto Orion with Sirius clock data Wiegand and I O ...
Page 60: ...60 14 4 72000207 Pluto Orion with IO Sirius Clock data Wiegand and Orbits ...
Page 61: ...61 14 5 72000304 Pluto with power supply and USB RS232 converter ...
Page 62: ...62 14 6 72000203 Pluto Orion with kpBus ...
Page 63: ...63 14 7 72000204 Orion with kpSensor bus ...
Page 64: ...64 14 8 72000602 Pluto Orion stacked with 8x RS485 Sirius i readers ...
Page 65: ...65 14 9 72000602 Pluto Orion with clock data or Wiegand readers ...
Page 66: ...66 14 10 72000602 Pluto Orion with RS485 readers kpBus combi ...