Tivok Energy T-HP20AB Heat Pump Installation Manual
PARAMETER
LISTING
Parameter
Scope
Default
Number
The incoming electric memorized sign
0 - not effective, 1 – effective 1
0
Daily circulation sign
0 - not effective, 1 – effective 1
1
Hot water tank differential temperature
2°C - 10°C
3°C
2
Faulty sensor temperature adjustment
0°C - 3°C
0°C
3
The interval for defrosting
15 - 99 min.
45
4
Defrosting on temperature
-9°C - 5°C
0°C
5
Defrosting off temperature
5°C - 20°C
10°C
6
Compressor’s exhaust air protection
90°C - 120°C
No setting
7
Evaporator coil temperature 1
-9°C 80°C
No setting
8
Discharge gas temperature 1
Unit: °C
No setting
9
Ambient temperature
-9°C ~ 80°C
No setting
10
Compressor continuous running time
0 - 99 min.
No setting
11
Fan continuous running time 1/4
Unit: seconds
No setting
12
Compressor auto-off code 1
No setting
13
On-off imported state
Special: sixteen
No setting
14
Maximum tank temperature set
40°C ~ 60°C
57°C
15
Auxiliary heat source
0 - not effective, 1 – effective 0
24
Water tank/water outlet temperature compensation
-5°C ~ 5°C
1°C
25
Evaporator coil temperature 2
-9°C ~ 80°C
No setting
29
Compressor auto-off code 2
No setting
32
Discharge gas temperature 2
Unit: °C
No setting
37
Start ambient temperature (auxiliary heat source)
2°C ~ 15°C
7°C
48
Numbers over 99 are represented by A for 100 and b for 110, i.e. A8 is 108 and b8 is 118.
For Parameters 13 and 32, the machine off codes are:
• 2: Water tank temp. sensor breakdown
• 3: Evaporator coil temp. sensor breakdown
• 4: Discharge temp. sensor breakdown
• 5: Discharge temp. is too high, switch off the unit
• 11: Anti-frozen finished, switch off the unit
• 12: High-pressure switch cutting
• 13: Meet set temp
• 14: Controller power off
• 19: Water flow switch breakdown
• 20: Defrosting preparation
• 21: Defrosting finish
• 22: Error phase or lack of phase with power supply,
then switch off the machine
• 27: Low-pressure switch cutting
• 22: High-pressure switch cutting during water tank
temp. is high
• 32: High-pressure switch cutting during defrosting
MANOMETER
INSTRUCTION
The manometer is a kind of high pressure equipment
and when the heat pump is on the manometer pointer
will point to the pressure value of refrigerant, with the
maximum value of protection being 42kg/Cm². When the
heat pump is off the pointer will point to the same value
as actual ambient temperature (e.g. 28°C) and related air
pressure (e.g.18kg/ Cm²).
Please check the manometer when you restart the heat
pump after not using it for a long time, if it shows an
ambient temperature smaller than 2°C, when the ambient
temp. is higher than 2°C, it means that refrigerant has
leaked a lot and you need to consult a technician.
Summary of Contents for T-HP20AB
Page 1: ...Installation and Operation Manual Tivok Energy Heat Pump T HP20AB...
Page 21: ...19 Tivok Energy T HP20AB Heat Pump Installation Manual CIRCUIT DRAWING MODEL T HP0AB...
Page 25: ...23 Tivok Energy T HP20AB Heat Pump Installation Manual CIRCUIT DRAWING MODEL T HP20AB...
Page 32: ...Tivok Energy T HP20AB Heat Pump Installation Manual 30 NOTES...
Page 33: ...31 Tivok Energy T HP20AB Heat Pump Installation Manual NOTES...