The injector is injecting, but it always stops at 50 gallon of product.
◆
Failure of Output Module 1 - check the voltage between Pin3 and Pin4 of Outputs P2, it should read >
20 VDC. If it is 0 VDC or below 1 VDC, replace the module.
◆
Failure of Output Module 2 - make sure the LED on Output Module 2 lights up (send confirmation
pulse back to the PLC) every 40-gallon of product pulses. If it does not light up, replace the module.
20.
Inconsistent calibration.
◆
Flow meter gears damaged – inspect and replace gears.
◆
Improper calibration check procedure – read Section 4 Field Calibration Instructions.
◆
Inconsistent pressure differential during calibration test – make sure the differential does not fluctuate
greatly during calibration test.