17
Lighting Schedule Interrupted Condition:
If the Hyperion
®
2 has been set to run a lighting schedule and the schedule
was interrupted for any reason (including a power failure), the remote
controller will show a CODE 10. This indicates that the lights were not on
for the entire scheduled time. The condition will automatically be cleared
when the next lighting schedule begins; this condition is also cleared if a
new lighting schedule is set.
Temperature Sensor Error:
If the Hyperion
®
2’s remote sensor is unable to get readings from its
temperature sensor it will turn off all load outputs. The remote sensor’s
LED will flash
red
twice periodically and the remote controller will show
CODE 20. If the problem is resolved, the controller will return to normal
functionality.
RH Sensor Errors:
If the Hyperion
®
2’s remote sensor is unable to get readings from its RH
sensor it will turn off all load outputs. The remote sensor’s LED will flash
red
once periodically and the remote controller will show CODE 21. If the
problem is resolved, the controller will return to normal functionality.
If the RH detector of the Hyperion
®
2’s remote sensor becomes saturated
with water, accurate readings are not possible. If this happens, all
load outputs will be disabled. The remote sensor’s LED will flash once
periodically and the remote controller will show CODE 22. Once the
remote sensor has dried out and accurate readings are possible, this
error condition will automatically be cleared and the controller will return to
normal functionality.
CO
2
Sensor Error:
If the Hyperion
®
2 is unable to get CO
2
readings from the CO
2
sensor, it will
turn off all load outputs. The remote sensors LED will flash
red
three times
periodically and the remote controller will show CODE 23. If the problem is
resolved, the controller will return to normal functionality.
Real Time Clock Error:
If the Hyperion
®
2’s remote sensor is unable to communicate with the on-
board real time clock (RTC), the load outputs will be disabled. The remote
sensor’s LED will flash
red
four times periodically and the remote controller
will show CODE 24. If the issue is resolved, the controller will resume
normal operation.