16
High Humidity Condition:
The Hyperion
®
2 displays a High Humidity warning by showing CODE 4:
this occurs when the room’s RH rises above 80% and remains there for 30
minutes. This condition is automatically cleared when the RH drops below
80%.
Low Humidity Condition:
The Hyperion
®
2 displays a Low Humidity warning by showing CODE 5:
this occurs when the room’s RH drops below 30% and remains there for 30
minutes. This condition is automatically cleared when the RH rises above 30%.
High CO
2
Concentration Condition:
If the CO
2
levels of the room rise above 5000 ppm, the Hyperion
®
2 will display
CODE 6. This condition is cleared when the CO
2
levels drop below 5000 ppm.
Empty CO
2
Tank Condition:
This feature informs the user when the CO
2
tank used to enrich the room
is empty. During the Daytime, if the CO
2
level is below the desired setpoint
(minus hysteresis) for 30 minutes or more, the Hyperion
®
2 will display
CODE 7. This condition is cleared when the CO
2
levels rise to the desired
setpoint.
No Measured Light Condition:
When the Hyperion
®
2 is set to have the Lights output active, the remote
sensor should detect light and begin using the Daytime control parameters.
If the light output has been active for 15 minutes and the remote sensor
does not measure light, it will display CODE 8 in the lower right-hand
corner of the screen. This is a useful feature that can inform the user that
there may be something wrong with the lights or that the remote sensor
is not placed properly. This code is automatically cleared when the photo
sensor detects light during daylight period.
No Measured Darkness Condition:
When the Hyperion
®
2 is set to have the Lights output off, the remote
sensor should NOT detect light and use the Nighttime control parameters.
If the light output has been off for at least 15 minutes and the remote
sensor measures light, it will display CODE 9 in the lower right-hand
corner of the screen. This is a useful feature that can inform the user that
unwanted light is present inside the room. This code is automatically
cleared when no light is detected.