Rated Voltage:
50 ... 36000 V AC / DC
Frequency range:
0 ... 200 Hz
Input resistance:
119 MΩ
Current peak value:
< 0.4 mA at 36000 V
Surge voltage strenght:
> 300 kV (test report available)
Indicator group:
I and III
Indication:
red LED for voltage > Limit Ut
green LED for standby / absent of voltage
two-line LCD with backlight white / red for indication of voltage,
frequency, type of voltage, and battery condition
acoustic signal at > Limit Ut
Limit Ut:
max. interference voltage. The value of Ut is labelled on the name plate.
Measurement ranges / Accuracy:
50 … 1000 V AC/DC ± 5% + 10 digits, resolution 1 V
1.00 … 9.99 kV AC/DC ± 5% + 10 digits, resolution 10 V
10.0 … 36.0 kV AC/DC ± 5% + 10 digits, resolution 100 V
automatic range switching
On-time:
15 min
Self-test:
function, grounding and protective resistors
Construction:
for indoor and outdoor installations,
IP 65, device can be used in moist environments
Operating temperature:
–15°C … + 55°
Power supply:
9 V block IEC 6LR61 / 6LF22 / 6LP3146 alkali-manganese
multi-stage battery indicator
Design:
two-pole voltage tester with fixed connection to ground
two-piece high-tension test probes, screwable, made of double-walled
GRP-tube with moulded resistor decade display part made of impact
resistant, dust proof plastic casing IP 65 with unbreakable display cover
10 m PUR cable with universal clip for condutor bars and
fixed ball points up to 25 mm
Standards:
EN/IEC 61243-2 high voltage tester
EN/IEC 60071 surge voltage strength
further applied standards:
EN/IEC 61010 and VDE 0105-100
(further details see risk analysis)
Test label:
date of the next examination on the sticker
repeated inspection at least every 6 years
Dimensions/weight:
2.1 kg / approx. 1430 x 100 x 100 mm
Transportation length demounted 900 mm
11. Technical data
18