TiEmme 2WAYS2 Technical Manual Download Page 3

 

 

 

 

 

 

Pag. 3 / 9 DMAN63W0000020-2Ways2 Manual - System100 Hydro STD2  

 

 

1

 

Introduction 

 

The Radio remote-control manages the functioning of the stove/boiler and monitors the state of operation in 
real time. The main characteristics are: 

Remote Control of the system with battery supply 
Room Thermostat embedded 

Parameters management of the control board 

 

 

 
Warnings: 

 

The  system  works  on  the  radio  band  ISM  433,92MHz.  The  transmission  and  receiving  distance  can  be 

reduced in case of a noisy environment: other devices as wireless headphones, video sender, toys or other 
devices could influence in the performances of the system. 

Check the presence of such instruments and make sure to turn them off in order to avoid electromagnetic 
waves pollution.  
If  more  remote  controls  are  nearby,  it  is  necessary  to  associate  the  remote  control  with  a  specific 

stove/boiler (see section 3, Settings Menu). 

Summary of Contents for 2WAYS2

Page 1: ...Pag 1 9DMAN63W0000020 2Ways2 Manual System100 Hydro STD2 Revision Date 11 12 2017 2WAYS2 RADIO CONTROL FOR SYSTEM100 HYDRO STD2 TECHNICAL MANUAL...

Page 2: ...System100 Hydro STD2 SUMMARY 1 INTRODUCTION 3 2 CONTROL PANEL 4 2 1 THE KEYS 4 2 2 THE DISPLAY 4 3 THE MENU 5 3 1 MAIN THERMOSTAT MODIFICATION 6 3 2 USER MENU 6 3 2 1 Chrono Menu 8 3 2 1 1 Chrono Moda...

Page 3: ...oard Warnings The system works on the radio band ISM 433 92MHz The transmission and receiving distance can be reduced in case of a noisy environment other devices as wireless headphones video sender t...

Page 4: ...ff completely the remote control and thus reduce the battery consumption This feature is to be used in case of prolonged non use of remote control If the function is activated the system uses the room...

Page 5: ...notifies that the planned hours of functioning parameter T67 is reached It is necessary to clean the stove or boiler Block Ignition The message appears if the system is turned off during Ignition afte...

Page 6: ...range 7 7 The default value is 0 Heating Management Boiler Thermostat It allows to modify the value of the Boiler Thermostat You can choose the minimum and maximum values by setting the corresponding...

Page 7: ...switch off the remote control and lower the battery consumption Description Display Push the SET button to enable the Standby mode To turn on the radio again first push the key and then the button tw...

Page 8: ...rs Menu Outputs Test Outputs Test Menu Restore Default Value Menu to restore the parameters values set by the manufacturer 3 2 1 Chrono Menu Menu to set the system ignition extinguishing times 3 2 1 1...

Page 9: ...e types of programming are stored separately if for example the Daily modality is set the other modalities are not changed Program Chrono Keys After choosing the favourite program Select the programmi...

Reviews: