segment should be set first, and the network setting should be selected on the menu interface of the
alarm control panel (such as: JB-TB-TC5126W wireless fire alarm control panel, etc.) that can be
equipped with the detector. After entering the network settings, first set the local address number, and
then set the detector network segment according to the actual situation on site (29 optional).
7.2. The device enters and exits the network:
A) Network access operation: When the control panel is in the "wireless registration interface" and the
alarm is not connected to the network, quickly press the setting button 3 times, the alarm will sound 3
times, and the green light will flash 3 times, and the module will report to the control panel Send the
network access application. After the application is successful, the total number of network access
displayed by the control panel +1.
B) Exit the network operation: When the control panel is in the "wireless registration interface" and the
module is in the network connection state, quickly press the setting button 3 times, the alarm will sound
3 times, and the green light will flash 3 times, the alarm will turn The control panel sends an exit
request. After the application is successful, the total number of exits displayed by the control panel is
+1.
C) Status detection: After the sounder is powered on, press the setting button once, and the green light
flashes once. If the control panel responds to the device and displays the loop and address number, it
indicates that the device has successfully connected to the network, otherwise the sounder is not
connected to the network. .
3. Equipment start: When the sounder receives the start signal from the control panel when it is in
normal working state, it will start the sound and light alarm output.
4. Equipment stop: when the alarm receives the stop signal from the control panel in the starting state, it
stops the sound and light alarm output.
5. Equipment reset: When the alarm receives the reset signal from the control panel when it is in the
starting state, it stops the sound and light alarm output, and the alarm is reset.
6. Restore factory settings: After the siren is connected to the network, when it is powered on again, the
working indicator will be on for 10s. During this period, the factory setting can be restored by pressing
the setting button 5 times. The working indicator flashes 3 times, and the factory restoration is
successful.
8.General faults and maintenance
Common faults and their solutions are shown in the following table:
Fault
Reason
Solution
According to the sensitivity
level of the control panel,
the yellow fault light will
flash once periodically
(75 seconds at level 1
Level 2 40 minutes
Level 3 2 and a half hours
Level 4 5 hours)
Too far away from the control
panel or interference sources
nearby cause communication
failure
Move the device near the control
panel, reconnect to the network
and remove the source of
interference
The faulty yellow light flashes 2
times periodically (every 48
seconds is a cycle)
Report a low battery fault
Replacement battery
After the device alarms, the
control panel has no status
prompt
The device is not connected to the
network
Restart the network operation
Device networking is
unsuccessful
Too far away from the control
panel or interference sources
nearby
Move the device near the control
panel, reconnect to the network
and remove the source of