TCSG5416W Wireless Sounder Installation manual

Ver1.3 202102

YINGKOU

 

TI

A

N

C

HENG

 

FIRE

 

PROTE

C

TION

 

EQUIPMENT

 C

O.,

 

LTD

4

segment should be set first, and the network setting should be selected on the menu interface of the
alarm control panel (such as: JB-TB-TC5126W wireless fire alarm control panel, etc.) that can be
equipped with the detector. After entering the network settings, first set the local address number, and
then set the detector network segment according to the actual situation on site (29 optional).
7.2. The device enters and exits the network:
A) Network access operation: When the control panel is in the "wireless registration interface" and the
alarm is not connected to the network, quickly press the setting button 3 times, the alarm will sound 3
times, and the green light will flash 3 times, and the module will report to the control panel Send the
network access application. After the application is successful, the total number of network access
displayed by the control panel +1.
B) Exit the network operation: When the control panel is in the "wireless registration interface" and the
module is in the network connection state, quickly press the setting button 3 times, the alarm will sound
3 times, and the green light will flash 3 times, the alarm will turn The control panel sends an exit
request. After the application is successful, the total number of exits displayed by the control panel is
+1.
C) Status detection: After the sounder is powered on, press the setting button once, and the green light
flashes once. If the control panel responds to the device and displays the loop and address number, it
indicates that the device has successfully connected to the network, otherwise the sounder is not
connected to the network. .
3. Equipment start: When the sounder receives the start signal from the control panel when it is in
normal working state, it will start the sound and light alarm output.
4. Equipment stop: when the alarm receives the stop signal from the control panel in the starting state, it
stops the sound and light alarm output.
5. Equipment reset: When the alarm receives the reset signal from the control panel when it is in the
starting state, it stops the sound and light alarm output, and the alarm is reset.
6. Restore factory settings: After the siren is connected to the network, when it is powered on again, the
working indicator will be on for 10s. During this period, the factory setting can be restored by pressing
the setting button 5 times. The working indicator flashes 3 times, and the factory restoration is
successful.

8.General faults and maintenance

Common faults and their solutions are shown in the following table:

Fault

Reason

Solution

According to the sensitivity

level of the control panel,

the yellow fault light will

flash once periodically

(75 seconds at level 1

Level 2 40 minutes

Level 3 2 and a half hours

Level 4 5 hours)

Too far away from the control

panel or interference sources

nearby cause communication

failure

Move the device near the control

panel, reconnect to the network

and remove the source of

interference

The faulty yellow light flashes 2

times periodically (every 48

seconds is a cycle)

Report a low battery fault

Replacement battery

After the device alarms, the

control panel has no status

prompt

The device is not connected to the

network

Restart the network operation

Device networking is

unsuccessful

Too far away from the control

panel or interference sources

nearby

Move the device near the control

panel, reconnect to the network

and remove the source of

Summary of Contents for TCSG5416W

Page 1: ... Please read the installation manual before installing and using the product TCSG5416W Wireless Sounder Installation manual YINGKOU TIANCHENG FIRE PROTECTION EQUIPMENT CO LTD ...

Page 2: ...of the working principle and the description of the sound pressure level in the technical indicators Ver1 2 30th Nov 2020 Wang Gang Optimize general fault description Ver1 3 5th Feb 2021 Liu Fen Change the appearance size picture according to the inspection requirements and increase the use time after battery undervoltage ...

Page 3: ...adio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consu...

Page 4: ... weighting 3 6 Modulation cycle 3 0S 4 0S 3 7 Flash frequency 1Hz 1 5Hz 3 8 Coding method automatically assigned by the control panel during networking 3 9 Communication method 470MHz FSK coded two way communication 3 10 Communication distance 50m 3 11 Transmitting power 20dBm 3 12 Reset method control panel reset 3 13 Use environment Type Indoor atmospheric pressure 86kPa 106kPa Temperature 0 55 ...

Page 5: ...ther the identification is complete 5 2 The way the sounder is fixed When installing use two screws to fix the base of the alarm on the 86 series width 72mm height 49mm depth 47mm embedded box and then install the sounder the installation hole distance is 60mm Figure 3 Installation hole distance 6 Test Warning Please make sure that the polarity of the battery is correct before proceeding 6 1 The s...

Page 6: ...cted to the network otherwise the sounder is not connected to the network 3 Equipment start When the sounder receives the start signal from the control panel when it is in normal working state it will start the sound and light alarm output 4 Equipment stop when the alarm receives the stop signal from the control panel in the starting state it stops the sound and light alarm output 5 Equipment rese...

Page 7: ...nal For example it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet 3 It should be installed in a low interference environment and far away from motors or large scale electrical equipment 10 File and warranty 10 1 Packing documents 1 Packing List 1 page 2 Instructions 1 copy 10 2 Warranty My company responsible for the maintenance of the product a problem...

Reviews: