TCSG5416W Wireless Sounder Installation manual
Ver1.3 202102
YINGKOU
TI
A
N
C
HENG
FIRE
PROTE
C
TION
EQUIPMENT
C
O.,
LTD
2
panel, work stably and reliably, and have good suppression ability against electromagnetic interference.
3.Technologic Charateristics
3.1. Battery model: CR17450-2-080-02
3.2. Rated working voltage: DC3V
3.3. Working current: monitoring current ≤45uA alarm current ≤240mA
.4. Indicator light:
Fault light: yellow, flashing periodically when communication fails
Working light: green, flashing periodically when communication is normal
3.5. Sound pressure level: 75dB ~ 115dB (A weighting)
3.6. Modulation cycle: 3.0S
~
4.0S
3.7. Flash frequency: 1Hz
~
1.5Hz
3.8. Coding method: automatically assigned by the control panel during networking
3.9. Communication method: 470MHz FSK coded two-way communication
3.10. Communication distance: ≤50m
3.11. Transmitting power: <20dBm
3.12. Reset method: control panel reset
3.13. Use environment:
Type: Indoor atmospheric pressure: 86kPa
~
106kPa
Temperature: 0℃
~
+55℃ Relative humidity ≤95%, non-condensing
3.14. Dimensions: 95mm×127mm×56mm
3.15. Shell material and color: ABS, red
3.16. Executive standard:
GB 26851-2011 "Fire Sound and/or Light Alarm"
XF 1151-2014 "General Requirements for Wireless Communication Functions of Fire Alarm
Systems"
4.Structural features and working principle
4.1
、
The outline diagram of the module is shown in Figure 1: