Please read the installation manual before installing and using the product

TCSG5416W Wireless Sounder Installation manual

YINGKOU TIANCHENG FIRE PROTECTION EQUIPMENT 
CO., LTD

Summary of Contents for TCSG5416W

Page 1: ... Please read the installation manual before installing and using the product TCSG5416W Wireless Sounder Installation manual YINGKOU TIANCHENG FIRE PROTECTION EQUIPMENT CO LTD ...

Page 2: ...of the working principle and the description of the sound pressure level in the technical indicators Ver1 2 30th Nov 2020 Wang Gang Optimize general fault description Ver1 3 5th Feb 2021 Liu Fen Change the appearance size picture according to the inspection requirements and increase the use time after battery undervoltage ...

Page 3: ...adio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consu...

Page 4: ... weighting 3 6 Modulation cycle 3 0S 4 0S 3 7 Flash frequency 1Hz 1 5Hz 3 8 Coding method automatically assigned by the control panel during networking 3 9 Communication method 470MHz FSK coded two way communication 3 10 Communication distance 50m 3 11 Transmitting power 20dBm 3 12 Reset method control panel reset 3 13 Use environment Type Indoor atmospheric pressure 86kPa 106kPa Temperature 0 55 ...

Page 5: ...ther the identification is complete 5 2 The way the sounder is fixed When installing use two screws to fix the base of the alarm on the 86 series width 72mm height 49mm depth 47mm embedded box and then install the sounder the installation hole distance is 60mm Figure 3 Installation hole distance 6 Test Warning Please make sure that the polarity of the battery is correct before proceeding 6 1 The s...

Page 6: ...cted to the network otherwise the sounder is not connected to the network 3 Equipment start When the sounder receives the start signal from the control panel when it is in normal working state it will start the sound and light alarm output 4 Equipment stop when the alarm receives the stop signal from the control panel in the starting state it stops the sound and light alarm output 5 Equipment rese...

Page 7: ...nal For example it cannot be installed in a metal box such as a fire hydrant box or outside of a metal cabinet 3 It should be installed in a low interference environment and far away from motors or large scale electrical equipment 10 File and warranty 10 1 Packing documents 1 Packing List 1 page 2 Instructions 1 copy 10 2 Warranty My company responsible for the maintenance of the product a problem...