APPENDIX
127
NV021 - Manual - 08 - 2012
DESCRIPTION
PARAMETER
UNIT
SETTING RANGE
U2> Breaker failure
U2>BF
OFF | ON
U2> Start relays
U2>ST-K
K1 | K2 | K3 | K4 | K5 | K6
U2> Trip relays
U2>TR-K
K1 | K2 | K3 | K4 | K5 | K6
U2> Start LEDs
U2>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
U2> Trip LEDs
U2>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
59V2 First threshold defi nite time
State
OFF | ON
Pickup value
Un
0.01 ... 0.50 step = 0.01
U2>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Overfrequency - 81O
f> Element
Setpoints
f> Logical block
f>BLK1
OFF | ON
f> Breaker failure
f>BF
OFF | ON
f> Start relays
f>ST-K
K1 | K2 | K3 | K4 | K5 | K6
f> Trip relays
f>TR-K
K1 | K2 | K3 | K4 | K5 | K6
f> Start LEDs
f>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5
f> Trip LEDs
f>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5
Defi nite time
81O First threshold defi nite time
State
OFF | ON
Pickup value
fn
1.000 ... 1.200 step = 0.001
f>def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Voltage control
f> Control enable
f>&
OFF | ON
f> Controlled by UE>>
f>&UE>>
OFF | ON
f> Controlled by digital input
f>&DIGIN
OFF | ON
f> Controlled by 27V1
f>&27V1
OFF | ON
f> Controlled by 59V2
f>&59V2
OFF | ON
f> Controlled by U<
f>&U<
OFF | ON
f> Controlled by 61850 network no link
f>&rete61850-KO
OFF | ON
f>& Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 200.0 step = 0.1
f> Control relays
f>&-K
K1 | K2 | K3 | K4 | K5 | K6
f> Control LEDs
f>&-L
START | TRIP | L1 | L2 | L3 | L4 | L5
f>> Element
Setpoints
f>> Logical block
f>>BLK1
OFF | ON
f>> Breaker failure
f>>BF
OFF | ON
f> Disabling by f>> start
f>disbyf>>
OFF | ON