CHARACTERISTICS
33
NV021 - Manual - 08 - 2012
Output relays
Six output relays are available (K1...K6)::
[1]
K1 and K2 have two changeover contacts (SPDT, type C).
K3, K4 and K5 have one make contact (SPST-NO, type A).
[2]
K6 has one break contact (SPST-NC, type B).
[3]
Each output relay may be programmed with following operating mode:
Operation MODE
(
No latched, Pulse, Latched
).
Logic
(
Energized/De-energized
).
To each output relay a programmable timer is matched (
Minimum pulse width
parameter).
All parameters are available inside the
Set\Relays
menu
.
Any change to the settings can be affected at any time, also with the relay on duty, separately for
each relay.
Notes:
When de-energized operating mode is set, the relay remains in rest condition if no trip command
is in progress.
When energized operating mode is set, the relay remains in operating condition if no trip command
is in progress and the auxiliary supply is powered on.
When no-latched operating mode is set (
Operation MODE
No latched
), the output relay reset
at the end of the trip condition. To each output relay a programmable timer is matched (minimum
pulse width operation).
When latched operating mode is set (
Operation MODE
Latched
), the output relay doesn’t reset
at the end of the trip condition; it stays ON until a reset command is issued (RESET key, ThySetter
or communication command).
When pulse operating mode is set (
Operation MODE
Pulse
), the output relay reset after a
t
TR
programmable delay regardless of the trip condition.
It is advisable to make sure that the output contact technical data are suitable for load (Nominal
current, breaking capacity, make current, switching voltage,...).
Matching every output relay to any protective element is freely programmable inside the
Setpoints
submenus according a tripping matrix structure.
[4][5]
Note 1 Schematic diagram are shown inside APPENDIX B1.
Note 2 K3 and K4 have a common terminal (A10)
Note 3 K5 and K6 have a common terminal (A13)
Note 4 Matching of the output relay to the protective and control functions can be defi ned so that any collision from other function is avoided.
All output relay are unassigned in the default setting.
Note 5 Self test relay: it is advisable to plan the following settings:
- Energized operating mode,
- No-latched ,
in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF.
—
•
•
•
•
•
•
•
•
•
•
•
Input
No-latched operation
Latched operation
Pulse operation
Output relay operation
Minimum pulse width
Relay-operation-timers.ai
t
Minimum pulse width
t
TR
t
TR
Input
No-latched operation
Latched operation
Pulse operation
Output relay operation
Minimum pulse width
Relay-operation-timers.ai
t
Minimum pulse width
t
TR
t
TR