
FUNCTION CHARACTERISTICS
70
NA20 - Manual - 04 - 2022
The second overcurrent element can be programmed with definite or inverse time characteristic by
setting the I> Time characteristic (
I>>Curve
) parameter (
DEFINITE, I2t
) available inside the
Set
\ Profile A(or B) \ Phase overcurrent-50/51 \
I>> Element \ Setpoints
menu.
The trip of
I
> element may be inhibited by the start of the second and/or third element (
I
>>,
I
>>>) by set-
ting
ON
the Disable I> by start I>>, Disable I>> by start I>>> (
I>disbyI>>, I>disbyI>>>
) parameters
available inside the
Set \ Profile A(or B) \ Phase overcurrent-50/51 \ I>> Element
(
I>>> Element) \ Setpoints
menus.
Similarly the trip of the
I
>> element may be inhibited by start of the third element (
I
>>>) by setting
ON
the Disable I>> by start I>>> (
I>>disbyI>>>
) parameter available inside the
Set \ Profile
A(or B) \ Phase overcurrent-50/51 \ I>>> Element \ Setpoints
menu.
All the named parameters can be set separately for
Profile A
and
Profile B
(
Set \ Profile A(or B) \
Phase overcurrent-50/51 \
I> Element
(
I>> Element
,
I>>> Element) \ Setpoints
menus).
An adjustable reset time delay is provided for every threshold (
t
>RES
,
t
>>RES
,
t
>>>RES
).
Each overcurrent element can produce the Breaker Failure output if the
I> BF
,
I>> BF
and/or
I>>> BF
parameters are set to
ON.
The parameters are available inside the
Set \ Profile A(or B) \
Phase overcurrent-50/51 \
I> Element
(
I>> Element
,
I>>> Element) \ Setpoints
menus.
[1]
For all overcurrent elements, a block from the second harmonic restraint may be set by setting
ON
the
I>2ndh-REST, I>>2ndh-REST, I>>>2ndh-REST
parameters inside the
Set \ Profile
A(or B) \ Phase overcurrent-50/51 \
I> Element
(
I>> Element
,
I>>> Element) \ Setpoints
menus.
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Element blocking
the
ICLP> Mode, ICLP>>
Mode
and/or
ICLP>>> Mode
parameters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Change setting
the
ICLP> Mode, ICLP>>
Mode
and/or
ICLP>>> Mode
parameters, whereas the operating thresholds within the CLP
may be adjusted inside the
Set \ Profile A(or B) \ Phase overcurrent-50/51 \
I> Element
,(
I>> Element
,
I>>> Element) \ Definite time (Inverse time)
menus.
For both operating modes the CLP Activation time parameters (
tCLP>, tCLP>>, tCLP>>>
) may
be adjusted inside the
Set \ Profile A(or B) \ Phase overcurrent-50/51 \
I> Element
(
I>> Element
,
I>>> Element) \ Setpoints
menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Timers-F50-51.ai
I> Start
I> Trip
t
>
t
>
RESET
INPUT
t
>RES
t
>RES
t
>RES
t
I> element phase overcurrent timers - 50/51
Summary of Contents for NA20
Page 207: ...APPENDIX 207 NA20 Manual 04 2022...