APPENDIX
198
NA20 - Manual - 04 - 2022
IE>> Enable
IE>> Enable
OFF | ON
IECLP>> Mode
IECLP>> Mode
OFF | ON - Element blocking | ON - Change setting
IECLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
tE>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IE>> Logical block
IE>>BLK1
OFF | ON
IE>> Input selective block
IE>>BLK2IN
OFF | ON
IE>> Output selective block
IE>>BLK2OUT
OFF | ON
IE>> Second harmonic restraint
IE>>2ndh-REST
OFF | ON
IE>> Breaker failure
IE>>BF
OFF | ON
IE> Disabling by IE>> start
IE>disbyIE>>
OFF | ON
IE>> Start relays
IE>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 |
IE>> Trip relays
IE>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 |
IE>> Start LEDs
IE>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
IE>> Trip LEDs
IE>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Definite time
50N/51N Second threshold definite time
State
OFF | ON
Pickup value
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>>def within CLP
IECLP>>def
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>>def Operating time
Value
s
0.03 ... 10.00 step = 0.01
IE>>> Element
Setpoints
IE>>> Enable
IE>>> Enable
OFF | ON
IECLP>>> Mode
IECLP>>> Mode
OFF | ON - Element blocking | ON - Change setting
IECLP>>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
tE>>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IE>>> Logical block
IE>>>BLK1
OFF | ON
IE>>> Input selective block
IE>>>BLK2IN
OFF | ON
IE>>> Output selective block
IE>>>BLK2OUT
OFF | ON
IE>>> Second harmonic restraint
IE>>>2ndh-REST
OFF | ON
IE>>> Breaker failure
IE>>>BF
OFF | ON
IE> Disabling by IE>>> start
IE>disbyIE>>>
OFF | ON
IE>> Disabling by IE>>> start
IE>>disbyIE>>>
OFF | ON
IE>>> Start relays
IE>>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 |
IE>>> Trip relays
IE>>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 |
IE>>> Start LEDs
IE>>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
IE>>> Trip LEDs
IE>>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Definite time
50N/51N Third threshold definite time
State
OFF | ON
Pickup value
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>>>def within CLP
IECLP>>>def
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01