APPENDIX
183
NA20 - Manual - 04 - 2022
I2> Trip LEDs
I2>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Definite time
46 First threshold definite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I2>def within CLP
I2CLP>def
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I2>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
Inverse time
46 First threshold inverse time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I2>inv within CLP
I2CLP>inv
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I2>inv Operating time
t2>inv
s
0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
I2>> Element
Setpoints
I2>> Enable
I2>> Enable
OFF | ON
I2CLP>> Mode
I2CLP>> Mode
OFF | ON - Element blocking | ON - Change setting
I2CLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I2>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I2>> Logical block
I2>>BLK1
OFF | ON
I2>> Input selective block
I2>>BLK2IN
OFF | ON
I2>> Output selective block
I2>>BLK2OUT
OFF | ON
I2>> Second harmonic restraint
I2>>2ndh-REST
OFF | ON
I2>> Breaker failure
I2>>BF
OFF | ON
I2> Disabling by I2>> start
I2>disbyI2>>
OFF | ON
I2>> Start relays
I2>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 |
I2>> Trip relays
I2>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 |
I2>> Start LEDs
I2>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
I2>> Trip LEDs
I2>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Definite time
46 Second threshold definite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 40.00 step = 0.01
I2>>def within CLP
I2CLP>>def
In
0.100 ... 0.999 step = 0.001
1.00 ... 40.00 step = 0.01
I2>>def Operating time
Value
s
0.03 ... 10.00 step = 0.01
Negative sequence current / positive sequence current ratio - I2/I1
I21> Element
Setpoints
I21CLP> Mode
I21CLP> Mode
OFF | ON - Element blocking | ON - Change setting
I21CLP> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1