MEASURES, LOGIC STATES AND COUNTERS
112
NA20 - Manual - 04 - 2022
Relays
For every output relay, the output operating state and diagnostic are available (
Read\Relays
menu):
• K1 State
ON/OFF
• K1 Diagnostic
OK/NOT OK
• K2 State
ON/OFF
• K2 Diagnostic
OK/NOT OK
•
......
• Kx State
ON/OFF
• Kx Diagnostic
OK/NOT OK
Counters
For every element two set of counters are available (Partial counters and Total counters); the partial
counters can be cleared by the user level, while the Total counter reset can be achieved with pass-
word (Session Level 1).
Every partial counter is reset to zero when ten thousand count is passed.
All partial counters can be cleared by means a single command; for this purpose the Reset partial
counters command must be issued (
Commands\Reset
submenu).
• 37 - counter
• 46 - counter
• I2/I1 - counter
• 49 - counter
• 50/51 - counter
• 50N/51N - counter
• 2ndh-REST - counter
• 74TCS - counter
• CB - counter
• 74CT - counter
• BF - counter
Partial counters
• xx Start partial counter (xx = I>, I>>,...)
0...9999
• xx Trip partial counter (xx = I>, I>>,...)
0...9999
• xx Block1 partial counter (xx = I>, I>>,...)
0...9999
• xx Block2 partial counter (xx = I>, I>>,...)
0...9999
Total counters
• xx Start total counter (xx = I>, I>>,...)
0...9999
• xx Trip total counter (xx = I>, I>>,...)
0...9999
• xx Block1 total counter (xx = I>, I>>,...)
0...9999
• xx Block2 total counter (xx = I>, I>>,...)
0...9999
Self test
Lower level diagnostic (MINOR) can be output or ignored; for this purpose the
MINOR Fail alarm
parameter can be set
ON
or
OFF
inside the
Set\Self test relay
submenu.
Following anomalies (MINOR) are not relevant (the protective elements continue to work):
• Errors concerning the digital fault recorder.
• Internal bus.
The self test information are:
• Protection and controls
ON SERVICE/OUT OF SERVICE
• System diagnostic
OK/NOT OK
• Device diagnostic
OK/NOT OK
• Program diagnostic
OK/NOT OK
• Data-base boot
OK/NOT OK
• Data-base runtime
OK/NOT OK
• DSP boot
OK/NOT OK
• DSP run-time
OK/NOT OK
• Memory boot
OK/NOT OK
• Memory run-time
OK/NOT OK
• Data Bus heavy
OK/NOT OK
• Data Bus minor
OK/NOT OK
• Oscillography run-time
OK/NOT OK
• PLC boot
OK/NOT OK
• PLC run-time
OK/NOT OK
• Protection I/O assigned verify startup
OK/NOT OK
• Protection I/O assigned verify run-time major
OK/NOT OK
• Protection I/O assigned verify run-time minor
OK/NOT OK
• Total protection I/O assigned not-matching
0
• Protection I/O assigned not-matching
• PLC I/O assigned not-matching
OK/NOT OK
• PLC I/O assigned not-matching run-time major
OK/NOT OK
• PLC I/O assigned not-matching run-time minor
OK/NOT OK
• Total PLC I/O assigned not-matching
0
• PLC I/O assigned not-matching
• MMI module Boot
OK/NOT OK
• MMI module Run-time
OK/NOT OK
• MRI module Boot
OK/NOT OK
• MRI module Run-time
OK/NOT OK
Summary of Contents for NA20