background image

Form RZ-NA-I-FT, Page 6

12”

(305mm)

Minimum

Venter Outlet Attachment Requirements:

A 4" to 3" vent reducer is required whenever 3" diameter
vent pipe is used on Sizes 30, 45, 60, or 75. See the Vent
Length Table in Paragraph No. 3.

A 4" to 5" vent increaser collar is required whenever 5" di-
ameter vent pipe is used on Sizes 45 and 60. See the special
venting requirements for a horizontal residential Category I
vent in Paragraph No. 3.

A minimum of 12" of straight pipe is required at the venter
outlet before installing an elbow in the vent system. An el-
bow should never be attached directly to the venter. An el-
bow attached to the straight pipe can be in any position at or
above horizontal. See Figure 5.

Model Size

30-125

150-250

300

Outlet Diameter

4"

5"

6"

Figure 5 - Alternate
Vent Directions

vent in any position
above horizontal

a minimum of 12"
(305mm) of straight
pipe is required before
an elbow

11. Venting

DANGER: Check the Model No. on the rating plate. If there is a suffix -LN or -CV, DO NOT USE these
venting instructions. Model FT heaters with either of these suffixes have special venting requirements;
follow the instructions in Form RZ 433-CV/LN.

WARNING: Units installed in multiples require individual vent pipe runs and vent caps. Manifolding
of vent runs is not permitted due to possible recirculation of combustion products into the building and
possible back pressure effects on the combustion air proving switch.

Venting must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning
Appliances and Equipment, and all local codes. Local requirements supersede national requirements.

These power-vented unit heaters are designed to operate safely and efficiently with either a horizontal or vertical vent. (Horizontal vent run is
recommended for maximum fuel savings.) Comply with the specific requirements and instructions in the following paragraphs.

If this heater is replacing an existing heater, be sure that the vent  is sized properly for the heater being installed. A properly sized vent system is
required for safe operation of the heater. An improperly sized vent system can cause unsafe conditions and/or create condensation. Do not vent into
an existing gravity vent or chimney.

Specific Venting Requirements (read all before installing)

1. Vent Pipe

 - The type of vent pipe required depends on the size of heater, the type of installation, and the vent configuration. Determine the vent

pipe type from the table below.
Vent pipe diameters are listed in the Maximum Permissible Vent Length Table in No. 3. Select the vent pipe type and one of the flue pipe diameter(s)
listed in the Table for the heater size being installed. If the vent being installed is a residential horizontal with Category I pipe, special vent pipe
diameter and length requirements apply.

2. Venter (Flue) Outlet

Venter
Outlet:

Type of Installation

Vent Configuration

Type of VENT Pipe Required

COMMERCIAL/

Horizontal Vent

Use either vent pipe approved for a Category III appliance

INDUSTRIAL

OR appropriately sealed 26-gauge galvanized steel or equivalent

(ANSI Z83.8 and

single-wall pipe.

CAN/C.G.A. 2.6) -

If local code requires, the terminal section may be double-wall pipe

Applies to all Sizes

with a single-wall vent run.

At least 1/2 of

 

the

Vent pipe listed above for a horizontal power-vented system

equivalent vent

may be used, OR vent pipe approved for a Category I heater

length is

 

Vertical

may be used. Single-wall pipe or double-wall (Type B) vent pipe
are suitable for use with a Category I heater.
If local code requires, the terminal section may be double-wall
pipe with a single-wall vent run.

RESIDENTIAL

Horizontal  or

Use either vent pipe approved for a Category III appliance OR vent

(IAS Requirement 10-96)

Vertical Vent

pipe approved for a Category I heater. Single-wall pipe or double-wall

 - 

Applies only to

(Type B) vent pipe are suitable for use with a Category I heater.

 Sizes 30, 45 and 60

(Special vent pipe size and vent length requirements apply to a
residential horizontal vent with Category I pipe.)

If local code requires, the terminal section may be double-wall pipe
with a single-wall vent run.

Summary of Contents for RENZOR FT 30

Page 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Page 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Page 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Page 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Page 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Page 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Page 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Page 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Page 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Page 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Page 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Page 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Page 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Page 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Page 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Page 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Page 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Page 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Page 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Page 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Reviews: