background image

Form RZ-NA-I-FT, Page 14

21. Check Installation & Start-up

Check the installation prior to start-up:

Check suspension. Unit must be secure and level.

Check clearances from combustibles. Requirements are shown in
Paragraph 6.

Check vent system to be sure that it is installed according to the
instructions in Paragraph 11.

Check piping for leaks and proper gas line pressure. Bleed gas lines
of trapped air. See Paragraph 12.

Check electrical wiring. Be sure all wire gauges are as recommended.
A service disconnect switch should be used. Verify that fusing or
circuit breakers are adequate for the load use.

Heater Start-Up:

WARNINGS: For your safety, read before
operating. If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.

• This appliance does not have a pilot. It is

equipped with an ignition device which auto-
matically lights the burner. Do not try to light
the burner by hand.

• Before operating, smell all around the appliance

area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will
settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

• Do not touch any electrical switch; do not use any

phone in your building.

• Immediately call your gas supplier from a

neighbor's phone. Follow the gas supplier's instruc-
tions.

• If you cannot reach your gas supplier, call your

fire department.

• Use only your hand to turn the gas control ON/

OFF knob or lever on the gas valve. Never use
tools. If the valve ON/OFF  knob or lever will
not turn by hand, do not try to repair it. Call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.

• Should overheating occur, or the gas supply fail

to shut off, turn off the manual gas valve to the
appliance before shutting off the electrical sup-
ply.

• Do not use this appliance if any part has been

under water. Immediately call a qualified ser-
vice technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.

Operating Instructions and Operating
Sequence

1. Set thermostat at lowest setting.

2. Turn off all electric power to the appliance.

3. This appliance is equipped with an ignition device which auto-

matically lights the burner. Do not try to light the burner by hand.
Open the access door and locate the gas control (ON/OFF) knob or
lever on the gas valve. (See Figure 11.)

4. Turn the gas control knob or lever clockwise to "OFF".

5. Wait five (5) minutes to clear out any gas. Then smell for gas,

including near the floor. 

If you smell gas, STOP!

 and follow the

steps in the 

WARNINGS

 printed on the left or on the Operating

Label on the heater. If you do not smell gas, proceed to the next
step.

6. Turn the gas control knob or lever counterclockwise to "ON".

7. Close the access door.

8. Turn on the electric power to the heater.

9. Set the thermostat to the desired setting.

NOTE:

 If the appliance does not operate, follow the instructions "To

Turn Off Gas to Appliance" printed below (and on the Operating La-
bel on the heater) and call your service technician.

10. Thermostat calls for heat, energizing the venter motor.

11. Venter pressure switch closes, firing the unit.

12. Burner flame is sensed and in 30 seconds, the fan motor is ener-

gized.

13. If the flame is extinguished during the main burner operation, the

integrated control system closes the main valve and must be reset
by interrupting power to the control circuit. (See lighting instruc-
tions on the heater.).

TO TURN OFF GAS TO THE APPLIANCE

1) Set thermostat to lowest setting

2) If service is to be performed, turn off all electric power to the

appliance.

3) Open the access door.

4) Turn the gas control knob or lever clockwise to "OFF". Do

not force.

5) Close the access door.

Gas Control Knob

(shown in the

ON position)

Gas Flow

Gas Control Lever

(shown in the

ON position)

Gas Inlet

Figure 11 - Gas Valve (Depending on the size and date
of manufacture, the heater
could have either of these
types of valves.)

Summary of Contents for RENZOR FT 30

Page 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Page 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Page 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Page 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Page 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Page 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Page 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Page 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Page 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Page 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Page 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Page 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Page 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Page 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Page 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Page 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Page 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Page 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Page 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Page 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Reviews: