27. Venter Motor

Remove dirt and grease from the motor housing. Power venter motor
is permanently lubricated.
The integrated circuit board controls and monitors operation of the
venter motor. If the contacts fail to close the venter motor will not run.
If the contacts fail to open, the venter motor will not shut off, prevent-
ing the combustion air pressure switch from opening.

28. Operating Gas Valve

The gas valve requires no field maintenance except careful removal
of external dirt accumulation and checking of wiring connections. In-
structions for testing pressure settings are in Paragraph 12.

WARNING: The operating valve is the prime safety
shutoff. All gas supply lines must be free of dirt or
scale before connecting to the unit to ensure positive
closure. See Hazard Levels, page 1.

29. Limit Control

I

f it is determined that the limit control needs replacing, use only a

factory-authorized replacement part that is designed for the size of
heater. To access the limit control on Sizes 30-75, remove the louver
assembly from the front of the heater. On Sizes 100-300, the limit
control is accessible in the control compartment.
Sizes 250 and 300 have an auxiliary limit control. To access the addi-
tional limit on Size 250 and 300 heaters, remove the fan guard.

For approximate limit locations, see Figure 12, page 15.

30. Combustion Air Pressure

Switch

See Figure 12, page 15, for location. If it is determined that the pres-
sure switch needs replacing, use only the factory-authorized replace-
ment part that is designed for the size of heater being serviced.

31. Flame Rollout Switch

Models FT 30, 45 and 60 are equipped with a flame rollout safety
switch. The flame rollout switch is a temperature activated manually
reset, limit switch. The switch is mounted on the side of the burner
box in a location that senses temperature in a central horizontal loca-
tion at the rear of the burner assembly.
If the flame rollout switch activates to shutdown the heater, the cause
must be corrected.
If it is determined that the flame rollout switch needs replacing, use
only the factory-authorized replacement part that is designed for use
on this heater.

32. Vent System

Check the vent system at least once a year. Inspection should include
all joints, seams, and the vent cap. Replace any defective parts.

Summary of Contents for RENZOR FT 30

Page 1: ...Follow the gas supplier s instructions If you cannot reach your gas sup plier call your fire department WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Page 2: ...be protected from damage by aircraft or other objects such as cranes and movable scaffolding In addition the heat ers must be located so as to be accessible for servicing adjustment etc 2 Warranty Re...

Page 3: ...100 square inches free area for each opening See 1 in Figure 2 2 Air from outside through duct openings 1 square inch free area per 2000 BTUH See 2 in Figure 2 3 Air direct from outside openings 1 squ...

Page 4: ...2 pt suspension Follow the illustrated instructions in Figure 3B Sizes 30 45 60 and 75 may be suspended with an optional ceiling sus pension kit Refer to Figure 3C Step by step instructions are includ...

Page 5: ...Composite drawings are not proportional for all sizes Field Wiring K 115V 60Hz 1Ph Connections L Thermostat Wires 24V Figure 4 Dimensions inches Size 30 45 60 75 100 125 150 200 250 300 A 28 5 8 28 5...

Page 6: ...ure that the vent is sized properly for the heater being installed A properly sized vent system is required for safe operation of the heater An improperly sized vent system can cause unsafe conditions...

Page 7: ...t system it is necessary to use 4 pipe only on a Size 30 and 5 pipe only on Sizes 45 and 60 Sizes 45 and 60 will require an increaser collar at the venter outlet The maximum horizontal vent length for...

Page 8: ...blems or unsafe conditions See the illustrations in Figures 7A and 7B for requirements of vertical and horizontal vent termination The vent terminal pipe may be either single wall or double wall Type...

Page 9: ...above a gas meter or service regulator Single Wall Vent Run and Single Wall Terminal End Single Wall Vent Run and Double Wall Terminal End 12 Gas Piping and Pressures WARNING This appliance is equippe...

Page 10: ...to correct settings by turning the regulator screw IN clockwise to increase pressure Turn regulator screw OUT counterclockwise to decrease pressure Derating by Manifold Pressure Adjustment for High A...

Page 11: ...Failed to Detect or Sustain Flame 3 Flashes Pressure Switch Open or Closed 4 Flashes High Limit or Flame Rollout Switch Open 5 Flashes Flame Sensed and Gas Valve Not Energized Steady On Internal Failu...

Page 12: ...OPEN CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS A...

Page 13: ...al probe which is electrically iso lated from ground When the flame impinges on the flame sensing probe the flame acts as a conduction path to ground The flame rectifies and completes the DC circuit a...

Page 14: ...r water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions an...

Page 15: ...dure 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1and B149...

Page 16: ...ulation Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 13 for replacement wiring requirements...

Page 17: ...ld cause fuel gas to spill out of the back of the burner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a...

Page 18: ...he front of the heater On Sizes 100 300 the limit control is accessible in the control compartment Sizes 250 and 300 have an auxiliary limit control To access the addi tional limit on Size 250 and 300...

Page 19: ...unded f Make certain integrated circuit board is grounded to ignitor g Circuit board not grounded g Make certain integrated circuit board is grounded to furnace chassis h Faulty integrated circuit boa...

Page 20: ..._____________________________ Unit Serial No __________________________________________ Date of Installation __________________________________________ PROBLEM PROBABLE CAUS E REMEDY No heat Heater 1...

Reviews: