INSTALLATION INSTRUCTIONS

To install the emergency backup power supplies, follow these steps:

1. 

Remove the unit from the packing box and inspect it for damage or imperfections. If any damage is found, do not install, replace it 

carefully into the packing box and notify the Thomas & Betts Product Support Hotline in Australia on 1300 666 595.

2.  If all looks okay proceed with the installation, use a pencil to mark the position of the mounting screw holes for the unit.

3. 

Depending on the wiring configuration, determine the cable entry or exit and remove the appropriate cable knockout(s).

4. 

Secure the unit to the wall/ceiling using appropriate fixings (not supplied) depending on the type of building construction material 

used.

WIRING CONNECTIONS

5.  Following below are the wiring connections of various models of remote power supplies. Ensure that the stripped wire ends are 

completely inserted into the terminal block and no bare conductors are exposed to the metal. Place the fuse into fuse holder before 

connecting unit to mains (fuse is placed inside the box and normally secure with the tape).

PS504:

 12V non-maintained 

unit specifically designed 

for lift to run 2x50 watt down 

lights. The output power on 

emergency is 50% of the rated 

power.

PS504M:

 12V maintained unit 

specifically designed for lift to 

run 2x50 watt down lights. The 

output power on emergency is 

50% of the rated power.

PS124:

 12V non-maintained 

unit designed for lift but can 

also be used remotely to 

provide escape lighting for 

large areas or to provide 

backup supply for the lighting 

up of difficult or hostile 

environments. The maximum 

load limit is 12W if used in a 

lift. The maximum load can be 

24W if using as backup supply 

to comply with AS/NZS2293.

PS404-NB:

 12V non-

maintained unit designed 

for lift but can also be used 

remotely to provide escape 

lighting for large areas or to 

provide backup supply for the 

lighting up of difficult or hostile 

environments. The maximum 

load limit is 40W if used in a 

lift. The maximum load can be 

80W if using as backup supply 

to comply with AS/NZS2293.

PS404M:

 12V maintained unit 

specifically designed for lift to 

run 2x20 watt down lights.

PS702-NB:

 12V non-

maintained unit designed to 

be used remotely to provide 

escape lighting for large areas 

or to provide backup supply 

for the lighting up of difficult 

or hostile environments. The 

maximum load limit is 35W if 

used in a lift. The maximum 

load can be 70W if using as 

backup supply to comply with 

AS/NZS2293.

Output to Lamp 1

Output to Lamp 2

Battery

Battery

PCA

PCA

PCA

Mains 240Vac 50Hz
Connect incoming unswitched active, 

neutral and earth to terminal marked 

US/A, N and E respectively

12V input from external transformer to  

run as a maintained unit

Output to Lamp 1

Output to Lamp 2

Battery

Battery

PCA

PCA

PCA

Mains 240Vac 50Hz
For switched illumination: Connect 

incoming switched active, unswitched 

active, neutral and earth to terminal 

marked S/A, A, N and E respectively
For permanent illumination: Connect 

incoming unswitched active, neutral 

and earth to terminal marked A, N 

and E respectively

(Note: Loop link between S/A and A)

Battery

PCA

Bell Connection (if used)

Output to load max 12W

Mains 240Vac 50Hz

Connect incoming unswitched active, 

neutral and earth to terminal marked 

US/A, N and E respectively

Battery

Battery

PCA

Output 12V DC

Battery

Battery

PCA

Mains 240Vac 50Hz
Connect incoming unswitched active, 

neutral and earth to terminal marked 

US/A, N and E respectively

12V input from external transformer to  

run as a maintained unit

Output 12V DC

Output to load max 40W 

(run up to 4 hours)

Battery

PCA

Output 

12V DC

Mains 240Vac 50Hz
Connect incoming unswitched active, 

neutral and earth to terminal marked 

US/A, N and E respectively

12V input from external transformer to  

run as a maintained unit

Mains 240Vac 50Hz
For switched illumination: Connect 

incoming switched active, unswitched 

active, neutral and earth to terminal 

marked S/A, A, N and E respectively
For permanent illumination: Connect 

incoming unswitched active, neutral 

and earth to terminal marked A, N 

and E respectively

(Note: Loop link between S/A and A)

Transformer

E

US/A

N

Bell DC

Lamp 2

Lamp 1

Bell Connection (if used)

Transformer

Bell Connection (if used)

Transformer

Lamp 2

Lamp 1

Bell DC

E

S/A

N

A

Transformer

US/A

N

E

Bell

-

+

Bell DC

Transformer

E

US/A

N

Bell DC

Transformer

E

S/A

N

A

Transformer

Output to load max 40W 

(run up to 4 hours)

Transformer

E

US/A

N

Output to load max 70W 