INSTALLATION INSTRUCTIONS
To install the emergency backup power supplies, follow these steps:
1.
Remove the unit from the packing box and inspect it for damage or imperfections. If any damage is found, do not install, replace it
carefully into the packing box and notify the Thomas & Betts Product Support Hotline in Australia on 1300 666 595.
2. If all looks okay proceed with the installation, use a pencil to mark the position of the mounting screw holes for the unit.
3.
Depending on the wiring configuration, determine the cable entry or exit and remove the appropriate cable knockout(s).
4.
Secure the unit to the wall/ceiling using appropriate fixings (not supplied) depending on the type of building construction material
used.
WIRING CONNECTIONS
5. Following below are the wiring connections of various models of remote power supplies. Ensure that the stripped wire ends are
completely inserted into the terminal block and no bare conductors are exposed to the metal. Place the fuse into fuse holder before
connecting unit to mains (fuse is placed inside the box and normally secure with the tape).
PS504:
12V non-maintained
unit specifically designed
for lift to run 2x50 watt down
lights. The output power on
emergency is 50% of the rated
power.
PS504M:
12V maintained unit
specifically designed for lift to
run 2x50 watt down lights. The
output power on emergency is
50% of the rated power.
PS124:
12V non-maintained
unit designed for lift but can
also be used remotely to
provide escape lighting for
large areas or to provide
backup supply for the lighting
up of difficult or hostile
environments. The maximum
load limit is 12W if used in a
lift. The maximum load can be
24W if using as backup supply
to comply with AS/NZS2293.
PS404-NB:
12V non-
maintained unit designed
for lift but can also be used
remotely to provide escape
lighting for large areas or to
provide backup supply for the
lighting up of difficult or hostile
environments. The maximum
load limit is 40W if used in a
lift. The maximum load can be
80W if using as backup supply
to comply with AS/NZS2293.
PS404M:
12V maintained unit
specifically designed for lift to
run 2x20 watt down lights.
PS702-NB:
12V non-
maintained unit designed to
be used remotely to provide
escape lighting for large areas
or to provide backup supply
for the lighting up of difficult
or hostile environments. The
maximum load limit is 35W if
used in a lift. The maximum
load can be 70W if using as
backup supply to comply with
AS/NZS2293.
Output to Lamp 1
Output to Lamp 2
Battery
Battery
PCA
PCA
PCA
Mains 240Vac 50Hz
Connect incoming unswitched active,
neutral and earth to terminal marked
US/A, N and E respectively
12V input from external transformer to
run as a maintained unit
Output to Lamp 1
Output to Lamp 2
Battery
Battery
PCA
PCA
PCA
Mains 240Vac 50Hz
For switched illumination: Connect
incoming switched active, unswitched
active, neutral and earth to terminal
marked S/A, A, N and E respectively
For permanent illumination: Connect
incoming unswitched active, neutral
and earth to terminal marked A, N
and E respectively
(Note: Loop link between S/A and A)
Battery
PCA
Bell Connection (if used)
Output to load max 12W
Mains 240Vac 50Hz
Connect incoming unswitched active,
neutral and earth to terminal marked
US/A, N and E respectively
Battery
Battery
PCA
Output 12V DC
Battery
Battery
PCA
Mains 240Vac 50Hz
Connect incoming unswitched active,
neutral and earth to terminal marked
US/A, N and E respectively
12V input from external transformer to
run as a maintained unit
Output 12V DC
Output to load max 40W
(run up to 4 hours)
Battery
PCA
Output
12V DC
Mains 240Vac 50Hz
Connect incoming unswitched active,
neutral and earth to terminal marked
US/A, N and E respectively
12V input from external transformer to
run as a maintained unit
Mains 240Vac 50Hz
For switched illumination: Connect
incoming switched active, unswitched
active, neutral and earth to terminal
marked S/A, A, N and E respectively
For permanent illumination: Connect
incoming unswitched active, neutral
and earth to terminal marked A, N
and E respectively
(Note: Loop link between S/A and A)
Transformer
E
US/A
N
Bell DC
Lamp 2
Lamp 1
Bell Connection (if used)
Transformer
Bell Connection (if used)
Transformer
Lamp 2
Lamp 1
Bell DC
E
S/A
N
A
Transformer
US/A
N
E
Bell
-
+
Bell DC
Transformer
E
US/A
N
Bell DC
Transformer
E
S/A
N
A
Transformer
Output to load max 40W
(run up to 4 hours)
Transformer
E
US/A
N
Output to load max 70W