Installation instructions for mains wire-in protectors
Neutral-earth warning light (LED units)
If the WARNING light is illuminated there is an excessive
voltage present between neutral and earth.
The WARNING light should never be illuminated
.
(a) Illumination at time of installation
If the WARNING light flashes as soon as the mains supply
to the ESP unit is turned on, one of the phase/live cables
may have been connected to neutral and the neutral to
phase/live.
Isolate or disconnect the ESP unit
immediately
. Check the phase/live and neutral
connections and if a mistake has been made, correct it.
If all the phase/live and neutral connections are correct,
there is a fault with the mains supply
(see (b) - below)
.
Note: The ESP unit may have suffered damage
- check the status indication
(see page 26)
.
(b) Illumination at any time
The WARNING light will flash when the neutral to earth
voltage exceeds 30 volts. The faster the flashing, the
higher the voltage between neutral and earth (at very
high voltages the WARNING light may appear to be
permanently illuminated).
Disconnect the ESP
protector immediately and check the mains supply
.
The ESP protector should not be reconnected until the
cause of the fault has been identified and rectified.
Note: The ESP unit may have suffered damage
- check the status indication
(see page 26)
.
Installation check (LED units)
The ESP unit should now be correctly installed. Switch the
power supply on. Check that a green LED per phase and
neutral is lit.
See Figure 16
. The unit is now fully operational.
Watch the WARNING light for 30 seconds. If it is flashing or lit
there is a problem with your installation
(see opposite)
.
PE
L
L'
L2
L2'
L3
L3'
N
N'
11
14
12
STATUS
L1
N
L3
L2
STATUS INDICATION
ESP 415D1
125 AgL
GREEN
FULL PROTECTION
GREEN & RED
REDUCED PROTECTION
(replace unit)
RED
NO PROTECTION
!
WARNING: If lit / flashing
disconnect unit & check
Neutral to Earth voltage
T2
C
T1
I
imp
4kA
I
n
20kA
I
max
oc
40kA
U
6kV
B
D
T3
EN/IEC 61643
PATENT
APPLIED
FOR
c
z
ac
U
280V 47-63H
Figure 16 - Status indication lights showing full protection on all
phases and neutral. On D1R units, status indication is shown on
the remote display unit.