Installation instructions for mains wire-in protectors
Connecting leads should be 10 mm
2
multi stranded
cable for parallel/shunt installation. For series installation,
refer to section 6.
For parallel/shunt installation, keep the connecting leads as
short as possible and ideally less than 25 cm (10 inches) in
length. For series installation, keep earth lead as short as
possible.
This may be better achieved with the equivalent D1R or
D1R/LCD unit with remote display mounting flexibility.
Bind the connecting leads tightly over their entire length.
Before installation
Check that the voltage between neutral and earth does
not exceed 10 volts.
If this voltage does exceed 10 volts, the installation
is unsafe.
Find and rectify the cause of this fault before proceeding.
(For delta supplies with no neutral,
see page 13
).
Make sure that the supply voltage is suitable for the unit.
8
9
10
1
2
Supply Rated
Unit Voltage
Voltage
Range
(V
RMS
)
(V
RMS
)
ESP 120 D1
Phase to
Neutral/Earth
110/120/127 90-150
ESP 208 D1 Series
Phase to Phase
190/208/220 156-260
ESP 240 D1
Phase to
Neutral/Earth
220/230/240 200-280
ESP 415 D1 Series
Phase to Phase
380/400/415 346-484
ESP 277 D1
Phase to
Neutral/Earth
240/254/277 232-350
ESP 480 D1 Series
Phase to Phase
415/440/480 402-600