Instruction Manual

Grounding

To ensure the maximum amount of protection for internal 
control components during possible power surge events, 
the recloser and control cabinet need to be solidly grounded 
together. The recloser ground conductor must be connected 
to the supplied #10–2 AWG ground lug located on the 
recloser’s frame base. All separate grounds should be 
connected to the main ground wire. All connections to the 
SEL

®

 control (including the control cable, which contains a 

ground) must be routed in close proximity to and parallel to 
the main ground paths and should be approximately equal 
in length. When using a power module with a 351R or 351R 
Falcon, the power module box must also be grounded. See 
Set-Up on 

QBHF

 for a visual representation.

WARNING:

  

Hazardous voltage. Recloser and control must 

be solidly grounded. Improper grounding can result in 
contact with high voltage, which will cause severe personal 
injury or death and equipment damage. Disconnecting the 
control cable when the recloser is energized could result in 
high voltage on the pins if the recloser tank is not grounded 
as specified.

Voltage Sensor Set-Up

All Elastimold

®

 MVRs come with pre-calibrated, load- 

side capacitive voltage sensors that are capable of 
measuring amplitude and phase angle with an accuracy  
of approximately 3% under normal operating conditions 
(-10˚ C to 45˚ C) and +/-5% at extreme conditions  
(-40˚ C to 65˚ C).  

For 3-phase MVRs, optional pre-calibrated line-side 
resistive voltage sensors are also available and are 
capable of measuring the voltage with a higher accuracy 
of approximately 1%. All sensors require an 8VAC LEA 
voltage sensor input on the SEL

®

 651Rx2 control. Refer 

to the Elastimold

®

 Source Side Voltage Sensor (ESSVS) 

Installation Instructions for mounting details. The ESSVS 
are not used with the SEL

®

 351R, 351R Falcon or 351RS 

Kestrel Controls.

Electronic Operation Test

Using the controller, open and close the MVR electrically by 
pressing the marked open and close buttons. Confirm that  
the selected button is in agreement with the position indicator 
on the control panel as well as the recloser position indicator. 
The recloser position indicator is located on the bottom of the 
recloser as shown below.

MVRs are designed to operate with a total circuit resistance  
of 6.5–7.3 ohms across the TRIP/CLOSE pins on the SEL

®

  

control interface.  

SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.

CAUTION:

 

 Do not energize the recloser for service until all 

control settings have been properly programmed and verified. 
Refer to the appropriate SEL

®

 control manual for programming 

procedures. Failure to comply may result in control and recloser 
misoperation.

WARNING:

  

Hazardous voltage. Do not rely on the contact 

position indicator to determine that the line has been 
de-energized. Always establish a visible disconnect and 
establish grounds when performing de-energized line work. 
Failure to follow proper safety practices can result in  
contact with high voltage, which can cause death or  
severe personal injury.

Individual Pole Position 

Indicator (Side View)

         Open Position   

  Closed Position   

      Open Position   

  Closed Position   

Individual Pole Position 
Indicator (Bottom View)

Summary of Contents for Elastimold Molded Vacuum Reclosers

Page 1: ...Instruction Manual MVR Molded Vacuum Reclosers 4 t 4 73...

Page 2: ...or shed replacement in the event of external damage t Specially formulated molded EPDM main body with overlapping silicone sheds for improved dielectric weatherability and UV performance t Integral C...

Page 3: ...38kV 3188C0115 21 Three Phase 15 27 38kV 3118C0114 22 Power Module for use with SEL 351R 3118C0116 23 SECTION 3 Design Test Data Elastimold MVR Test Data Summary 24 Description of Operation The singl...

Page 4: ...17 1 29 3 38 Nominal Frequency Hz 50 or 60 50 or 60 50 or 60 Phase Spacing on 3 Phase Units Inches 15 5 15 5 15 5 BIL kV 150 150 170 Power Frequency Withstand Dry kV 50 60 70 Power Frequency Withstand...

Page 5: ...ly can result in death severe personal injury and equipment damage CAUTION All MVRs are sealed and leak tested prior to shipment to prevent moisture ingress Do not open the lower cover as it is possib...

Page 6: ...e when opening packaging not to nick or cut the EPDM silicone insulation on the MVR After uncrating visually inspect the MVR for any shipping damage including the insulation bushings trip lever mounti...

Page 7: ...t 32 pin cable should be used to connect the power module to the MVR The recloser receives the necessary signal to open and close from the control circuitry The control is powered from an external sup...

Page 8: ...ractices when lifting and mounting the MVR Use lifting rings on three phase units and lift smoothly limiting shifting to avoid damage Do not lift three phase MVRs by the side terminals as damage could...

Page 9: ...plied with the recloser control Please refer to the appropriate SEL control manual Each recloser and control cabinet assembly comes with standard interconnection cables that are keyed at each end to a...

Page 10: ...ltage sensors are also available and are capable of measuring the voltage with a higher accuracy of approximately 1 All sensors require an 8VAC LEA voltage sensor input on the SEL 651Rx2 control Refer...

Page 11: ...ormal operation with the recloser in service loss of vacuum or a defective module may be indicated by excessive AM radio noise with the recloser open or by measuring a difference in surface temperatur...

Page 12: ...silicone insulation is not prone to the cracking or chipping that sometimes occurs with porcelain or epoxy insulators However should damage occur as a result of an external event in most cases it is...

Page 13: ...PROVED CHECKED DRAWN DATE DATE DATE MATERIAL FINISH DRAWING TITLE SCALE DRAWING NUMBER SHT SIZE SHT No NEXT ASS Y ENGINEERING SPEC QUALITY STD MATERIAL STD 29 38 746 2 12 93 328 5 10 06 255 6 2 77 70...

Page 14: ...ND THE INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS...

Page 15: ...ECKED DRAWN DATE DATE DATE MATERIAL FINISH DRAWING TITLE SCALE DRAWING NUMBER SHT SIZE SHT No NEXT ASS Y ENGINEERING SPEC QUALITY STD MATERIAL STD 31 18 791 9 12 93 328 5 10 06 255 6 2 77 70 3 23 99 6...

Page 16: ...E INFORMATION CONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL...

Page 17: ...D MATERIAL STD 1 50 38 1 15 01 381 3 1 75 44 5 35 13 892 2 1 75 44 5 15 50 393 7 15 50 393 7 24 25 616 1 12 95 328 9 33 76 857 6 16 44 417 6 42 56 1081 19 56 496 8 3188C0112 2 REV ECN DESCRIPTION BY C...

Page 18: ...ETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT THOMAS BETTS PROPRIETARY RIGHTS DRAWING NUMBER REV 3188C0112 2 MVR3 RECLOSER WITH LINE SIDE AND LOAD SIDE ARRESTER...

Page 19: ...D MATERIAL STD 1 50 38 1 15 01 381 3 1 75 44 5 35 13 892 2 1 75 44 5 15 50 393 7 15 50 393 7 24 25 616 1 12 95 328 9 35 57 903 5 18 25 463 6 42 56 1081 19 56 496 8 3188C0113 2 REV ECN DESCRIPTION BY C...

Page 20: ...TTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT THOMAS BETTS PROPRIETARY RIGHTS DRAWING NUMBER REV 3188C0113 2 MVR3 RECLOSER WITH LINE SIDE AND LOAD SIDE ARRESTER FRAMES PENDING ECN 11 30...

Page 21: ...AND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT THOMAS BETTS PROPRIETARY RIGHTS DRAWING NUMBER REV ENGINEERING SPEC QUALITY STD MATERIAL STD ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW T...

Page 22: ...RATE LIMIT SWITCHES ASSOCIATED WITH THE MANUAL TRIP LEVER 69 LIMIT SWITCH 3 10 000 1 VOLTAGE RATIO 4 CAPACITIVE VOLTAGE SENSORS ARE INTEGRATED INTO THE MVR 5 RESISTIVE VOLTAGE SENSORS ARE ADD ON MODUL...

Page 23: ...11 27 12 JMG LOAD SIDE SOURCE SIDE ELASTIMOLD MVR THREE PHASE RECLOSER 32 PIN CONTROL CABLE SEL 351R RECLOSER CONTROL N P R R5 R4 12 22 R7 R6 I 3 A S I 1 I2 I B D IN C J K C1 C2 L M G 1 I 2 I NOTE 2 Y...

Page 24: ...rcuits within their respective rated maximum voltages 17 1kV for 15kV units and 29 3kV for 27kV units L7 73T are certified for use as a single phase device capable of single phase tripping on grounded...

Reviews: