THERMOSTAHL MULTIPLEX MCL Instruction Manual Download Page 19

8. GENERAL MAINTENANCE INSTRUCTIONS 

 

In  conformity  with  DIN  4575  and  4756  regulations  the  periodic  cleaning  (even  daily  if  it’s 
necessary) of the boiler, must be performed by a qualified personnel to ensure an economic and 
ecologic running.  
The  boiler  needs  a  maintenance  operation  to  be  done  at  the  end  of  the  winter  season.  Special 
care  should  be  given  to  cleaning  of  the  smoke  tubes,  to  avoid  the  laying  of  carbon  which  can 
damage them.  
If a correct maintenance is not performed, then problems will arise such as:  

 

Performance dropping  

 

Increased fuel consumption  

 

Increasing temperature of exhausts  

 

Carbon layers  

 

Reduced draught  

 

Maintenance instructions 

 

 

Disassemble the burner (if necessary).  

 

Open the doors.  

 

Disassemble the turbulators from the fire tubes and clean them with a special brush.  

 

Clean the walls of the combustion chamber with a special crowbar.  

 

Empty the ash tray.  

 

Check  the  insulation  bands  and  the  glass  fiber  braids  and  replace  them  in  case  of 
deterioration.  

 

Check the refractory material on the door.  

 

The  safety  valves  and  the  temperature/pressure  relief  valve  must  be  checked  and 
replaced in case of malfunction.  

 

Check the water connections.  

 

Check the draught regulator .  

 

Check the filter from the water supply.  

 

Check the eye slit thermoresistant glass.  

 

 

Summary of Contents for MULTIPLEX MCL

Page 1: ...MULTIPLEX MCL INSTRUCTION MANUAL ver 1 1...

Page 2: ...tory The name THERMOSTAHL means GUARANTEE for the buyer THERMOSTAHL provides heating solutions for more than 20 years on the market The production experience and the expertise gives us the opportunity...

Page 3: ...TIVES SPECIFICATIONS 3 PREFACE 4 1 DESCRIPTION 5 2 DELIVERY TRANSPORT 5 3 FEATURES OF THE BOILER MULTIPLEX 9 4 BOILER LOCATION 12 5 CHIMNEY 14 6 BOILER ASSEMBLING 16 7 CONTROL PANEL 16 8 MAINTENANCE G...

Page 4: ...Electrical conections between burner and boiler Standard 763 Central heating boilers Minimum dimensions of the combustion chamber Standard 234 Central heating boilers Terminology nominal power techni...

Page 5: ...Familiarize yourself with its operations and controls and follow strictly the instructions given If you have any questions or you need more information about particular points concerning the THERMOSTA...

Page 6: ...is designed in such a way that all the surfaces that come in contact with the flame to be cooled by water including the grid where the ash and the remains of burning are The two ways of exhaust from t...

Page 7: ...e the boiler during transport on the transport means so as not to slip Consider seriously that the gravity centre is above the geometric centre That means there is need of a special care during transp...

Page 8: ...780 210 209 180 2 360 11 370 x 625 1150 600 0 37 900 230 233 200 2 420 13 5 370 x 625 1400 600 0 37 900 260 256 220 2 450 14 370 x 625 1400 600 0 37 900 290 291 250 3 620 17 370 x 625 1100 950 0 37 14...

Page 9: ...480 295 130 2 260 910 1600 1850 1900 810 1730 610 100 1570 930 1500 1480 295 130 2 290 1100 2000 2000 1840 1000 2250 830 150 1570 930 1250 1210 345 130 2 350 1100 2000 2000 2090 1000 2250 830 150 2160...

Page 10: ...ucing the number of ignition starts of the burner in case of adapting of a burner Reliability Energy savings Enviromental friendly Modern Design Solid Construc ion Easy maintenance Big fire box Large...

Page 11: ...d pipe that crosses the rear plate and the combustion chamber and which has an optimal length to ensure a better air intake The ventilator is controled by the control panel and the conection of the ve...

Page 12: ...ned in such a way that all its parts in touch with flames to be cooled by water The profile number and length of the smoke pipes are designed specially for a maximal exploitation of the exhausts The w...

Page 13: ...ance fireproof doors and without woods for windows The boilers having the caloric flow of 0 1 Gcal h can be located in rooms having other destinations in which it will be arranged an appropriate space...

Page 14: ...would be listed the work instructions that will consider the speciffic of the boilers in the room There will be also listed internal instructions concerning the operators task and the way of operatin...

Page 15: ...ds grass etc The cleaning of the chimney esspecially in the exit points from the boiler and the elbows where the exhaust gases change their course A clean chimney means a correct draught The insulatio...

Page 16: ...sons for malfunction of solid fuels boilers 1 Small active height of the chimney 2 Untight masonry of the chimney 3 Too narow masonry of the chimney 4 The existence of foreign parts or narowing of the...

Page 17: ...70 boilers we have only one cover for the sides For the other boiler series we have two or three covers for the sides 7 THE CONTROL PANEL Digital Electronic Controller PWC 1000 Operating instructions...

Page 18: ...maximum exhaust temperature that the fan power starts to decrease 08 IGNITION TIME Maximum time of the process ignition Fan power is determined only by the ignition air setting at this process 09 IGNI...

Page 19: ...ng Increased fuel consumption Increasing temperature of exhausts Carbon layers Reduced draught Maintenance instructions Disassemble the burner if necessary Open the doors Disassemble the turbulators f...

Reviews: