Settings
01
TEMP.WATER
Maximum water temperature.
02
TEMP.EXHAUST
Maximum exhaust temperature.
03
TEMP.CIRCULATOR
Water temperature that the circulator pump starts to operate.
04
TEMP.Bypass
Water temperature that the bypass valve starts to operate.
05
FAN AIR MAX
Maximum power amount of the fan (%) in the full burning process.
06
DT WATER
Temperature difference below the maximum water temperature that the fan
power starts to decrease.
07
DT EXHAUST
Temperature difference below the maximum exhaust temperature that the
fan power starts to decrease.
08
IGNITION TIME
Maximum time of the process “ignition”. Fan power is determined only by the
“ignition air” setting at this process.
09
IGNITION AIR
Power amount of the fan (%) in the ignition process.
10
Off TIME
Time that exhaust temperature must be below the “11-Off exhaust” so that
the controller is set into “end of fuel” process.
11
Off EXHAUST
Exhaust temperature value that determines when the fuel has ended.
12
CONS.PERIOD
Repeating time of the process “flame conservation”. In this process the fan
power works at “09-ignition air” so that the flame is conserved.
13
CONS.DURATION
Duration of the process “flame conservation”.