Flame extinguish
Check the pellet is in the tank.
Check if the motorreductor and spiral for the pellet
Call the service
No pellet
Check the pellet is in the tank.
No pellets in the tank - fill the pellet tank.
It is also possible that the following notification appears (not an eror for boiler):
Fehler in Parametern
(Greška u parametrima) /
Error in parameters
The following errors are written only in the memory of regulation and do not show up on the
screen
Ignition (Power ON)
Error memory has been initialized
Error example
Resetting the errors
You can annul the errors by pressing the
QUIT
key.
Before that you need to check the cause of the error and try to remove it. If it is not possible, call an
authorized service center.
To reset the error, press QUIT. (SET button)
Fr 2018-4-6 09:59
ERROR:
BOILER OVERHEATED
STB ACTIVATED
QUIT
Fr 2018-4-6 09:59
ERROR:
SMOKE FAN FAULT
QUIT