47
BUFFER
Chose BUFFER and press key SET
BUFFER
- NOT AVALIABLE
- 2 SENS
Chose 2SENS(with 2 sensors) ,
press key SET
BUFFER
BUFFER setP.temP.
50*C
WORK: 60*C
BUFFER TEMP.:
set the temperature in the storage tank
(temperature on the lower sensor)
which when the boiler is reached the
boiler goes off.
BUFFER LOAD
BOILER setP. temP.
at buffer charge
78*C
WORK: 78*C
BUFFER LOAD:
set temperature for loading buffer
(outgoing boiler temperature)
BUFFER
RESIDUAL heat to
boiler temP. under
65*C
WORK: 65 *C
Set the temperature for extinguishing the
tank pump
BUFFER LOAD
boiler temP. PUMP ON
50*C
WORK: 58*C
Setting the temperature at which the
storage tank filling pump is on
BUFFER LOAD
Buffer temP. hyst
5*C
WORK: :5*C
Adjusting the storage tank temperature
hysteresis - the difference in temperature
between the upper and lower sensor after
which the boiler swiches on/off
BUFFER
Reisdual heat diff.
temp. Bolier-Buffer
5*C
WORK: :5*C
BUFFER:
Temperature difference between Boiler and
Buffer