Page 18
No ACTION
Possible problem/cause
Solution
3.
NO
Ignition components not operating properly.
Check connection between cable & IGN
electrode.
Check IGN electrode spark gap.
Check IGN electrode for discharge to ground
(break in ceramic).
Check IGN cable for damage
Increase distance between IGN cable and all
metal parts. Check that spark does not
discharge to ground at location of spark plug
connection. Shorten cable if possible. If
applicable, provide extra insulation with silicon
hose etc.
Spark will occur each
second.
NO
IGN sequence stops, no pilot flame.
No reaction to transmitter command (receiver
does not react).
Press RESET button, see instructions.
Add ground wire between pilot burner and gas
valve.
Do not coil the IGN cable.
Shorten IGN cable if possible.
NO
IGN sequence stops, no pilot flame.
Transmitter command is possible.
IGN sequence stops, no pilot flame.
Transmitter command is possible.
OK
4.
Pilot lit.
NO
TC and SW cable reversed.
Check connection of cable to receiver and
interrupter, see fig. 1.
Impulse magnet not operating properly.
Replace gas valve.
Short between interrupter and SW cable.
Check connection to interrupter.
OK
No gas (magnet unit drops after 30 second
audible count).
Check gas supply to gas valve.
5.
Sparking stops after pilot
is lit
NO
Short between interrupter and TC cable.
Check connection to interrupter, see fig. 1
OK
Electronic measuring amplifier defective.
Replace receiver.
Interrupter
Receiver
Summary of Contents for Trimline 2050 OH
Page 20: ...Page 20...
Page 32: ...Pag 32 A...
Page 33: ...Pag 33 20 m m B C D E F G...
Page 34: ...Pag 34 I J 50 20 H...
Page 35: ...Pag 35...
Page 36: ...Pag 36...
Page 37: ...Pag 37...
Page 38: ...Pag 38...
Page 39: ...Pag 39...
Page 40: ...Pag 40 Thermocet International B V Laagerfseweg 31 3931 PC Woudenberg www thermocet nl...