background image

8

 

C

ARACTÉRISTIQUES

 

TECHNIQUES

 / 

T

ECHNICAL

 S

PECIFICATIONS

 

* The cooling capacity can change considerably depending on the humidity and air termperature.

** Optional EC Axial fan for cooling from 10°C instead of 20°C ambient temperature.

Nominal ton

 

2,2

 

4,8

 

4,8

 

9,5

 

Model

 

C

8

C

17

CR

17

CR

34 

Capacity Cooling mode*

 

Cooling Capacity

 

Btu/h

 

28 000

 

58 000

 

58 000

 

111 000

 

W

 

8 200

 

17 000

 

17 000

 

32 800

 

Capacity Heating mode*

 

Heating Capacity

 

Btu/h

 

58 000

 

111 000

 

W

 

20 000

 

32 800

 

Electrical data

 

Power supply

 

V

-

PH

-

Hz

230

-

1

-

50

 

380

-

3

-

50

 

380

-

3

-

50

 

380

-

3

-

50

 

Rated power Input

 

W

 

3 300

 

5 500

 

5 500

 

13 000

 

Performance

 

Air Circulation (High 
speed)

 

m3/h

 

1 500

 

4 500

 

4 500

 

7000

 

Indoor external static 
pressure

 

Pa

 

100

 

100

 

100

 

100

 

Indoor Coil

 

Number of rows

 

3

 

3

 

3

 

3

 

Fin spacing

 

mm

 

2,3

 

2,3

 

2,3

 

2

 

inch

 

3/32

 

3/32

 

3/32

 

3/32

 

Special

 

Grooved Tube

 

Grooved Tube

 

Grooved Tube

 

Grooved Tube

 

Louvered fins

 

Louvered fins

 

Louvered fins

 

Louvered fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

Tube diameter

 

mm

 

Ф

9.54

 

Ф

9.54

 

Ф

9.54

 

Ф9.54

 

inch

 

3/8

 

3/8

 

3/8

 

3/8

 

Indoor fan

 

Type

 

Centrifugal Blower

 

Centrifugal Blower

 

Centrifugal Blower

 

Centrifugal Blower

 

No. used

 

1

 

1

 

1

 

2

 

Diameter

 

mm

 

Ф280

mm

 

Ф355

mm

 

Ф355

mm

 

Ф355

mm

 

inch

 

11

 

14

 

14

 

14

 

Drive type

 

DIRECT

 

DIRECT

 

DIRECT

 

DIRECT

 

No. motors

 

1

 

1

 

1

 

2

 

Motor output

 

W

 

240

 

315

 

315

 

315

 

Motor rpm

 

r/min

 

2600

 

1780

 

1780

 

1 780

 

Compressor

 

Type

 

Rotary

 

Scroll

 

Scroll

 

Scroll

 

Quantity

 

1

 

1

 

1

 

1

 

Model

 

PA331X3CS

 

C

-

SBP205H38

C

-

SBP205H38

C

-

SCP400H38

Brand

 

GMCC

 

PANASONIC

 

PANASONIC

 

PANASONIC

 

Capacity

 

Btu/hr

 

28 000

 

58 000

 

58 000

 

111 000

 

Input

 

W

 

3 300

 

5 500

 

5 500

 

11 000

 

Rated current(RLA)

 

A

 

13

 

10,3

 

10,3

 

20

 

Refrigerant oil charge

 

TYPE 

-

 mL

 

ESTER OIL VG74 · 1100

 

FV 68S 

-

 1600

 

FV 68S 

-

 1600

 

 

Outdoor Coil

 

Number of rows

 

2

 

2

 

2

 

2

 

Fin spacing

 

mm

 

1,8

 

1,8

 

1,8

 

2

 

inch

 

0,0709

 

0,0709

 

0,0709

 

0,0709

 

Special

 

Grooved Tube

 

Grooved Tube

 

Grooved Tube

 

Grooved Tube

 

Louvered fins

 

Louvered fins

 

Louvered fins

 

Louvered fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

hydrophilic aluminum fins

 

Tube diameter

 

mm

 

Ф

9.54

 

Ф

9.54

 

Ф

9.54

 

inch

 

3/8

 

3/8

 

3/8

 

3/8

 

Outdoor Fan

 

Type

 

Axial

 

Axial

 

Axial

 

Axial

 

No. used

 

1

 

1

 

1

 

1

 

Diameter

 

mm

 

Ф450

 

Ф

630

 

Ф

630

 

Ф800 

inch

 

17,8

 

24,8

 

24,8

 

32

 

Drive type

 

Direct

 

Direct

 

Direct

 

Direct

 

No. motors

 

1

 

1

 

1

 

1

 

Motor model

 

ATE804S

 

ATE808S

 

ATE808S

 

ATE810AP

 

Motor output

 

W

 

420

 

520

 

520

 

1 250

 

Motor rpm

 

r/min

 

1350

 

900

 

900

 

700

 

Refrigerant

 

Type

 

R410A

 

R410A

 

R410A

 

R410A

 

Refrigerant volume

 

kg

 

2,1

 

3,6

 

3,6

 

7,2

 

Refrigerant Control

 

EEVX

 

EEVX

 

EEVX

 

EEVX

 

Dimensions(W×H×D)

 

mm

 

900x1150x1700

 

1200x1400x1800

 

1200x1400x1800

 

1200x2050x2250

 

inch

 

35x45x67

 

47x55x71

 

47x55x71

 

47x81x88

 

Net Weight

 

kg

 

200

 

305

 

305

 

600

 

Ibs

 

386

 

672

 

672

 

1 322

 

Summary of Contents for C17

Page 1: ... Compressors High Efficiency Able to withstand ambient temperature cooling from 20 C to 45 C R410A Optional EC fan for Cooling from 10 C to 45 C Analogic Pressure Transducer Phase sequence relay protected against re versed phases for 3 phase models Room temperature sensor thermostat Low noise level ...

Page 2: ...2 Copyright All technical information in this manual as well as drawings and diagrams are our property and may not be reproduced without our prior written permission ...

Page 3: ...ational purposes only and speak only as of the date of issue thereof The manufacturer is responsible for the compliance of the apparatus with the rules directives and construction stan dards at the time of marketing Knowledge and compliance with legal provisions and standards inherent in the design implementation installation commissioning and maintenance are the exclusive responsibility of the co...

Page 4: ...gerous situa tions In the case of a long period of non operation disconnect the power supply of the device When putting into operation it is advisable to call in qualified personnel Generally all repair work or maintenance should be performed only by authorized and trained personnel Caution Electrical components running mechanisms can cause injury To protect themselves from these risks during inst...

Page 5: ...uit is completely waterproof and allows the unit to operate in areas with a maximum ambient temperature of 45 C At high ambient temperatures above 45 C the cooling of the condenser air flow is too low and a high pressure stops the HP switch The pressure switches HP BP will reset automatically after a few minutes At an ambient temperature below 20 C moisture in the airflow can form ice on the evapo...

Page 6: ...r duct 3m isolated changes the tempera ture inside the pipe by 5 C The sheaths result in a loss that s why we must always put straight Fig 1 In case of deviation avoiding signifi cant bends bends 45 Fig 2 prefer them large curves fig 3 Place the air distribution duct cooled as close to the ceiling the cold air will descend slowly to the ground and will be returned to the air conditioner through th...

Page 7: ...l heat generating sources in the air conditioned room Do not cover fig 6 or obstruct the rear of the air conditioner fig 7 Keep a free and clear area for a good air circulation allowing the correct operation of the conditioner fig 8 9 If the air does not circulate well the unit switches to safety Poor repeated use causes irreversible damage Always ensure that the exhaust ducts fig 10 or air intake...

Page 8: ...14 14 14 Drive type DIRECT DIRECT DIRECT DIRECT No motors 1 1 1 2 Motor output W 240 315 315 315 Motor rpm r min 2600 1780 1780 1 780 Compressor Type Rotary Scroll Scroll Scroll Quantity 1 1 1 1 Model PA331X3CS C SBP205H38 C SBP205H38 C SCP400H38 Brand GMCC PANASONIC PANASONIC PANASONIC Capacity Btu hr 28 000 58 000 58 000 111 000 Input W 3 300 5 500 5 500 11 000 Rated current RLA A 13 10 3 10 3 2...

Page 9: ...9 Dimensions C8 Dimensions C17 CR17 ...

Page 10: ...10 Dimensions CR34 ...

Page 11: ...of the room thermostat compressor and safety Security Management High pressure Security Management Low pressure Security Management sub cooling Security Management overheating Safety temperature management Controlling the cooling unit from room thermostat Viewing cooling unit values A Reset default B Page scrolling up C Page scrolling down D Valid E Idle display shows the status of the thermostat ...

Page 12: ...gerant right on the outlet of the evaporator SUBCOOLING 4 C Show the value of the subcooling that is equal to Temparature of condensation minus liquid temperature on the outlet of the condenser ensure that expansion valve has 100 liquid refrigerant SUPHEATING 3 5 C Show the value of the superheating that is equal to Temparature of evaporation minus gas temperature on the outlet of the evaporator e...

Page 13: ...ire replace the wire or check the sensor replace the sensor 8 SENSOR T2 ERROR Reconnect the temperature sensor right on the liquid side of the outdoor heat exchan ger check the sensor Check wire replace the wire or check the sensor replace the sensor 9 SENSOR T3 ERROR Reconnect the temperature sensor right on the liquid side of the indoor heat exchanger check the sensor Check wire replace the wire...

Page 14: ...14 SCHEMA ELECTRIQUE ELECTRICAL WIRING C8 Cooling only ...

Page 15: ...15 C8 Cooling only EC AXIAL FAN VERSION ...

Page 16: ...16 SCHEMA ELECTRIQUE ELECTRICAL WIRING C17 Cooling only ...

Page 17: ...17 CR17 Cooling and heating SCHEMA ELECTRIQUE ELECTRICAL WIRING ...

Page 18: ...18 CR17 Cooling and heating ...

Page 19: ...W PRESSURE TRANSDUCER 10 SUCTION SIDE TEMPERATURE SENSOR 11 HIGH PRESSURE TRANSDUCER 12 SCHRADRE VALVE HIGH SIDE 13 OUTDOOR HEAT EXCHANGER TEMPERATURE SENSOR 14 FILTER 15 OUT COMPRESSOR TEMPERATURE SENSOR 16 COMPRESSOR 17 SCHRADRE VALVE LOW SIDE 18 INDOOR HEAT EXCHANGER TEMPERATURE SENSOR 19 ELECTRONIC EXPANSION VALVE 20 INDOOR HEAT EXCHANGER 21 INDOOR CENTRIFUGAL FAN ...