TROUBLESHOOTING
#1 WAIT TEMPO START
Unit is waiting to finish its safety time after a cycle
360 SEC
It is causes by restarting the unit too early, thermostat trigger, and after a unit reset
#2 WAIT
Thermostat is OFF or not in demand in either cooling or heating mode
REGULATION OFF
#3 OUTDOOR TOO LOW
Outdoor temperature is too low for the compressor to run in cooling mode : Min tempe-
rature to start 20°C, cut at 18°C ( start 10°C for EC axial version)
TEMPERATURE
Outdoor temperature is too low for the compressor to run in heating mode : Min tempe-
#4 PHASE REVERSAL
For three phases compressor, phases are not well connected
Reconnect the phase in the right order
#5 SENSOR PHP / ERROR
Reconnect the sensor, check the high pressure sensor
#6 SENSOR PBP / ERROR
Reconnect the sensor, check the low pressure sensor
#7 SENSOR T1 / ERROR
Reconnect the compressor output temperature sensor, check the sensor
Check wire, replace the wire or check the sensor, replace the sensor
#8 SENSOR T2 / ERROR
Reconnect the temperature sensor right on the liquid side of the outdoor heat exchan-
ger , check the sensor
Check wire, replace the wire or check the sensor, replace the sensor
#9 SENSOR T3 / ERROR
Reconnect the temperature sensor right on the liquid side of the indoor heat exchanger ,
check the sensor
Check wire, replace the wire or check the sensor, replace the sensor
#10 SENSOR T4 / ERROR
Reconnect the temperature sensor right on the gas side of the indoor heat exchanger,
return to compressor , check the sensor
Check wire, replace the wire or check the sensor, replace the sensor
#11 SENSOR T5 / ERROR
Reconnect the outdoor temperature sensor, check the sensor
Check wire, replace the wire or check the sensor, replace the sensor
#12 DEFAULT HP
Temperature High pressure to high > 36 bar
PRESS RESET
Need to press reset (round arrow)
#13 DEFAULT BP
Temperature Low Pressure too low < 3,8 bar
PRESS RESET
Need to press reset (round arrow)
#14 DEFAULT THP
Temperature of discharge is too high >100°C
PRESS RESET
Need to press reset (round arrow)
Summary of Contents for C17
Page 9: ...9 Dimensions C8 Dimensions C17 CR17 ...
Page 10: ...10 Dimensions CR34 ...
Page 14: ...14 SCHEMA ELECTRIQUE ELECTRICAL WIRING C8 Cooling only ...
Page 15: ...15 C8 Cooling only EC AXIAL FAN VERSION ...
Page 16: ...16 SCHEMA ELECTRIQUE ELECTRICAL WIRING C17 Cooling only ...
Page 17: ...17 CR17 Cooling and heating SCHEMA ELECTRIQUE ELECTRICAL WIRING ...
Page 18: ...18 CR17 Cooling and heating ...