![THERMOBILE C17 Manual Download Page 12](http://html.mh-extra.com/html/thermobile/c17/c17_manual_1105471012.webp)
12
MENU
DESCRIPTION
COMPRESSOR ON
Everything is running fine, shown after 20s of inactivity on the touchpad
HEATING
COMPRESSOR ON
Everything is running fine, shown after 20s of inactivity on the touchpad
COOLING
COMPRESSOR ON
Unit is in defrost mode, shown after 20s of inactivity on the touchpad
DEFROST
Unit goes in defrost when heating and THP-TBP>55°C and Toudoor <9°C for 60 sec
HP 27,5/46,5/50/3,5
Shows High Pressure, Temperature of condensation ( relative to pressure of refrigerant),
temperature of liquid on the outlet of the condenser, subcooling value
BP 7,2/-1/3/4
Shows Low Pressure, Temperature of evaporation ( relative to pressure of refrigerant),
temperature of gas on the outlet of theevaporator,superheating value
P.HP 27,5 bar
Shows High Pressure value
P.BP 7,2 bar
Shows Low Pressure value
P.HP 27,5 bar
Show High Pressure value
T.out Comp 50°C
Show discharge temperature of compressor
T.out Cond 50°C
Show value of the liquid refrigerant right on the outlet of the condenser
T.out Evap -3°C
Show value of thegas refrigerant right on the outlet of the evaporator
SUBCOOLING 4°C
Show the value of the subcooling, that is equal to Temparature of condensation minus liquid
temperature on the outlet of the condenser, ensure that expansion valve has 100% liquid
refrigerant
SUPHEATING 3,5°C
Show the value of the superheating, that is equal to Temparature of evaporation minus gas
temperature on the outlet of the evaporator, ensures the suction of the compressor is 100%
gaseous
INPUT AIR 25°C
Shows temperature of air on the inlet of the indoor coil (return air from room)
OUTDOOR AIR 30°C
Show temperature of outdoor air, sensor is placed on thegrill of the axial fan of the outside
heat exchanger.
COOLING 15H
Shows how long the unit has been running on cooling mode, if the unit is capable of doing it
HEATING 10H
Shows how long the unit has been running on heating mode, if the unit is capable of doing it
POS. VALVE 54%
Shows current position of the EEV (Electronic expansion valve)
SPEED FAN 100%
Not in use right now
EER 4,85
Shows current EER in COOLING mode
P 17,0KW
Shows output power based on extrapolation (for information use only)
COP 3,85
Shows current COP in HEATING mode
P 17,0KW
Shows output power based on extrapolation (for information use only)
Summary of Contents for C17
Page 9: ...9 Dimensions C8 Dimensions C17 CR17 ...
Page 10: ...10 Dimensions CR34 ...
Page 14: ...14 SCHEMA ELECTRIQUE ELECTRICAL WIRING C8 Cooling only ...
Page 15: ...15 C8 Cooling only EC AXIAL FAN VERSION ...
Page 16: ...16 SCHEMA ELECTRIQUE ELECTRICAL WIRING C17 Cooling only ...
Page 17: ...17 CR17 Cooling and heating SCHEMA ELECTRIQUE ELECTRICAL WIRING ...
Page 18: ...18 CR17 Cooling and heating ...