4-10 AutoXP Users Guide
Thermo Fisher Scientific
HART
D/A Trim [475 key sequence 1, 2, 3]
D/A Trim is used to calibrate the 4-20mA output of the AutoXP MVT.
The associated method will automatically run and request a user to connect a
reference meter to measure the current on the 4-20mA current loop.
Points are calibrated at 4mA and 20mA as follows:
1. After selection of D/A Trim, a warning is provided to remove the AutoXP
MVT output from any automatic control.
Figure 4-15. Warning
-
L
oop
should be
removed from automatic control
2.
The user is requested to connect a reference meter for
L
oop calibration.
Figure 4-16. Connect reference meter