A. Inputs
Power supplies
Line voltage is applied between the “S1” and “N1” quick connect terminals. 24 VAC Class II
Transformer secondary voltage supplied to X and C
Limit switch
The 120 VAC optically isolated limit switch input is connected on pin P2-1 & 9. Refer to the Heat
Mode section for the control operation.
Thermostat call for heat “W”
24 VAC thermostat input. A call for heat is recognized when the thermostat connects “W” to “R”. This
input has an indicator LED that will light when the control receives a call for heat. Refer to the Heat
Mode section for the control operation.
Thermostat call for cool, “Y”
24 VAC thermostat input. A call for cooling is recognized when the thermostat connects “Y” to “R”. This
input has an indicator LED that will light when the control receives a call for cooling. Refer to the Cool
Mode section for the control operation.
Thermostat call for dehumidification “DEHUM”
24 VAC thermostat input. A call for dehumidification is recognized when the humidistat connects
“DEHUM” to “R”. This input has an indicator that will light when the control receives a call for
dehumidification. Refer to the Cool Mode section for the control operation.
Thermostat call for fan “G”
24 VAC thermostat input. A call for fan is recognized when the thermostat connects “G” to “R”. This
input has an indicator LED in that will light when the control receives a call for fan. Refer to the Fan
Mode section for the control operation.
B. Outputs
PSC Control
The control shall control a five speed indoor blower motor. Rating shall be 10 FLA, 30 LRA @ 120
VAC. Connections are made via 0.250 x 0.032” male quick connect terminals labeled “HEAT”,
“COOL”, and “LOW”. “HEAT” is energized when the heat speed blower is to run. “COOL” is energized
when the Cool speed blower is to run. “LOW” is energized during a call for fan is received or a call for
dehumidification is received.
Oil Burner
Control
The control provides dedicated contacts to operate the T-T input of an oil primary control.
Rating shall be class 2 – 24 VAC pilot duty @ 24 VAC (<200mA).
Power
The switched 120 VAC power from the LIMIT switch passes through the board between Pins 1 & 2
of connector P1.
Compressor contactor
The control provides switched 24VAC to operate a compressor contactor. Rating shall be class 2 – 24
VAC pilot duty @ 24 VAC (<200mA).
EAC (electronic air cleaner)
The control provides a 120 VAC output for an electronic air cleaner. This output is energized whenever
the fan motor is energized (either low, heat or cool speed). Connection is made via male quick connect
terminal labeled “EAC”.
Summary of Contents for OD6FA072D48B
Page 5: ...2...
Page 61: ...58 VIII Sequence of Operations Flow Chart...
Page 62: ...59...
Page 63: ...60 IX Trouble Shooting Flow Chart...
Page 64: ...61...
Page 65: ...62...
Page 66: ...63...
Page 67: ...64...
Page 69: ...66 Appendix A Replacement Parts Replacement Parts for OD6F 072D...
Page 70: ...67...
Page 71: ...68 Replacement Parts for OD6R 072D...
Page 72: ...69...
Page 73: ...70 Appendix B Wiring Diagrams OD6 A072D48 PSC Wiring Diagram...
Page 74: ...71 OD6 A072DV5 ECM Wiring Diagram...
Page 75: ...72 OD6 X072DV5 ECM 2 Stage Wiring Diagram...
Page 76: ...73...