8. As a final step in the installation, the appliance must be adjusted to deliver a temperature rise within
the range of 50° to 80°F. Adjust the blower motor speed to obtain a temperature rise within the
acceptable range. The required blower speed will depend on the airflow resistance of a supply and
return air duct systems.
Fig. 9: Supply air duct sizing Example
The
RETURN AIR DUCT SYSTEM
should equal the warm air duct system in airflow capabilities.
NOTE:
When a return register is located in the same room as the furnace, the register must be at least 20
feet away from the furnace.
SIZING THE DUCT WORK FOR A COMBINATION HEATING AND COOLING SYSTEM:
Two formulas must be used in determining the CFM requirements of a combustion heating and cooling
system.
1. HEATING CFM:
HEAT OUTPUT OF FURNACE (BTUH)
1.1 X TR (TEMPERATURE RISE, °F) =
HEATING(CFM)
EXAMPLES:
A. 110,000 BTUH OUTPUT
1.1 X 85°F TR = 1176 CFM FOR HEATING
B. 110,000 BTUH OUTPUT
1.1 X 70°F TR = 1429 CFM FOR HEATING
2. COOLING CFM: 400 CFM X COOLING TONNAGE (12,000 BTUH PER TON)=AIRFLOW FOR
COOLING(CFM)
EXAMPLES:
A. 400 CFM X 3 TON (12,000 BTUH) = 1,200 CFM FOR COOLING
1TON
B. 400 CFM X 2.5 TON (12,000 BTUH) = 1,000 CFM FOR COOLING
1 TON
IMPORTANT: SIZE THE DUCT SYSTEM FOR THE LARGER OF THE TWO AIRFLOW
REQUIREMENTS.
Summary of Contents for OD6FA072D48B
Page 5: ...2...
Page 61: ...58 VIII Sequence of Operations Flow Chart...
Page 62: ...59...
Page 63: ...60 IX Trouble Shooting Flow Chart...
Page 64: ...61...
Page 65: ...62...
Page 66: ...63...
Page 67: ...64...
Page 69: ...66 Appendix A Replacement Parts Replacement Parts for OD6F 072D...
Page 70: ...67...
Page 71: ...68 Replacement Parts for OD6R 072D...
Page 72: ...69...
Page 73: ...70 Appendix B Wiring Diagrams OD6 A072D48 PSC Wiring Diagram...
Page 74: ...71 OD6 A072DV5 ECM Wiring Diagram...
Page 75: ...72 OD6 X072DV5 ECM 2 Stage Wiring Diagram...
Page 76: ...73...