Unit Description
26
Zone 1 Cool, Zone 2 Cool, and
Zone 3 Heat
The CIS is closed so high pressure refrigerant
vapor leaves the compressor and flows through
the hot gas line and the open HGS3 into the
Zone 3 evaporator. There the refrigerant heats the
Zone 3 evaporator and condenses into high
pressure liquid. Because the SLS3 is closed, the
liquid refrigerant flows through the LRCV3 and
the remote liquid line to LLS and LLS2.
The LLS is open so some of the refrigerant flows
through the Zone 1 expansion valve into the
Zone 1 evaporator. There the liquid refrigerant
cools the Zone 1 evaporator as it evaporates into
low pressure vapor. The refrigerant returns to the
compressor through the SLCV, and the
accumulator.
The LLS2 is also open so some of the refrigerant
flows through the Zone 2 expansion valve into the
Zone 2 evaporator. There the liquid refrigerant
cools the Zone 2 evaporator as it evaporates into
low pressure vapor. The refrigerant returns to the
compressor through the SLS2, the suction line, the
SLCV2, and the accumulator.
Host Unit and Zone 1 Evaporator
1. Liquid Line Solenoid (LLS)—Open
2. Liquid Return Check Valve (LRCV)—Closed
3. Suction Line Check Valve (SLCV)—Open
4. Suction Line Solenoid (SLS)—Open
5. Hot Gas Solenoid (HGS)—Closed
6. Condenser Inlet Solenoid (CIS)—Closed*
7. Condenser Inlet Check Valve
(CICV)—Closed
8. Receiver Tank Pressure Solenoid
(RTPS)—Open*
9. Condenser Check Valve (CCV)—Closed
10. Bypass Hand Valve
11. Purge Valve (PV)—Open*
12. Purge Check Valve (PCV)—Open
* The microprocessor will open and close these
valves as required to control the head pressure or
compensate for high ambient temperatures.
Zone 2 Evaporator
1C. Zone 2 Liquid Line Solenoid (LLS2)—Open
2C. Zone 2 Liquid Return Check Valve
(LRCV2)— Closed
3C. Zone 2 Suction Line Check Valve
(SLCV2)— Open
4C. Zone 2 Suction Line Solenoid (SLS2)—Open
5C. Zone 2 Hot Gas Solenoid (HGS2)—Closed
Zone 3 Evaporator
1R. Zone 3 Liquid Line Solenoid (LLS3)—Open
2R. Zone 3 Liquid Return Check Valve
(LRCV3)— Open
3R. Zone 3 Suction Line Check Valve
(SLCV3)— Closed
4R. Zone 3 Suction Line Solenoid
(SLS3)—Closed
5R. Zone 3 Hot Gas Solenoid (HGS3)—Open
Summary of Contents for 002008
Page 4: ...4 ...
Page 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Page 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Page 114: ...Mechanical Diagnosis 114 ...
Page 116: ...Electric Standby Diagnosis 116 ...
Page 120: ...Remote Evaporator Specifications 120 ...
Page 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Page 128: ...Remote Evaporator Electrical Maintenance 128 ...
Page 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Page 134: ...Remote Evaporator Structural Maintenance 134 ...
Page 136: ...Remote Evaporator System Diagnosis 136 ...
Page 140: ...Index 140 ...
Page 142: ......
Page 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Page 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Page 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Page 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Page 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Page 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Page 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Page 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Page 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Page 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Page 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...