Once you have completed all the preparatory steps,
proceed as follows to start up the boiler for the first time:
- If the system is equipped with a temperature controller
or timer thermostat, make sure that it is switched on.
- Adjust the timer thermostat/s or temperature controller
to the desired temperature (~20° C).
- Turn the system’s main power switch ON.
- Make the required adjustments as described in the
instruction manual specific to the control panel.
Turn the control panel power switch ON and make sure
that the green power indicator lights.
The burner should now ignite and remain in operation until
the set temperature is reached.
If any ignition faults or malfunctions occur, the burner
performs a “LOCKOUT SHUTDOWN”. This is shown by
the red button light on the burner and by the warning
light on the control panel.
b
If a “LOCKOUT SHUTDOWN” occurs, wait about
30 seconds before resetting the burner.
To reset the burner, press the red button light on the
burner and wait until the flame ignites.
Repeat this operation 2 -3 times at the most. If the prob-
lem persists, perform the following checks:
- All checks listed in the burner’s own instruction
manual;
- All steps listed in the ‘Preparing for Initial Start-up’
section;
- All the electrical connections shown on the control
panel wiring diagrams.
ON
OFF
33
ENGLISH
TECHNICAL ASSISTANCE SERVICE
INITIAL START-UP