b
The stack must guarantee the minimum draught
specified by applicable technical standards,
assuming zero pressure at the connection to the
flue gas exhaust.
b
Inadequate or badly dimensioned stacks and exhausts
can increase combustion noise, cause condensation
problems and affect combustion parameters.
b
Joints must be sealed using appropriate materials
(e.g. filler, mastic or silicone based sealant).
b
Uninsulated flues are potentially dangerous and
can cause burns.
BOILER DOOR HINGES
CHANGING THE DIRECTION OF DOOR OPENING
The boiler door hinges are factory fitted on the right of the door. If you need to reverse the direction of opening, remove
the boiler’s side panel and proceed as follows.
The boilers has 3 hinge points so that the direction of opening of the door can be rapidly reversed.
Once you have checked that the default direction of opening is as required, or have reversed the direction of opening as
instructed in the ‘Changing the direction of door opening’ section, remove the spare hinge assembly ‘B’ (bolt (1), bushing
(3) and washer (2)) opposite the hinged side of the door.
A
B
Axis of door rotation
A
1
2
3
24
ENGLISH
INSTALLER