background image

15

A. Duct Fitting Equivalent

Quantity

Fitting

Equivalent

Description

Length

1

6" Dia to 3-1/4" x 10"

  1 Ft.

2

3-1/4" x 10" 90

°

 elbows

  (2 @ 10 feet)

20 Ft.

1

3-1/4 x 10" Wall cap
  (Model# 12551)

 2 Ft.

Total "A" Duct Fitting Equipment 23 Ft.

B. Straight Duct Length

1

15 Ft.of 3-1/4 x 10"
  rectangular duct

15 Ft.

1

1 Ft. of 3-1/4" x 10"
  rectangular duct

1 Ft.

1

6 Ft. of 3-1/4 x 10"
rectangular duct

6 Ft.

Total "B" Straight Duct Length

22 Ft.

C. Total Equivalent Straight =23+22=45 Ft.

Once you've determined the value of C, refer to Chart 1
for internal blower (Page 16) to find the minimum C.F.M.
for 3-1/4" x 10" rectangular duct. Note that the chart
legend furnishes different lines for different ducting sizes
and shapes.  By using the correct line, you can see that 45
feet of rectangular duct equates to approximately 420
C.F.M.

BLOWER DUCT SIZING

Based on the blower position, determine the
required straight duct length and size, and the
number and types of elbows or transitions.

Calculate the total equivalent length using this
equation: A+B = C

A = Duct fitting 

equivalent 

straight length (use Table 1,

Page 17).

B = Straight duct length of smallest duct used.

C =

 Total equivalent straight

length of the smallest size

ducting used.

Use the value of C from Chart 1, Page 16 (Internal
Blower) or Chart 2 (Remote Blower) to determine the
C.F.M.

NOTE:  We recommend a minimum of 350 cubic
feet per minute (C.F.M.)  Flow for the range
downdraft system.

FOR EXAMPLE:  An internal ventilation system, using
model VTN30RQ, would have a total equivalent length of
45 feet when using fittings noted on Page 17.

Figure 23B - Top View of 3-1/4" x 10" Adapter

in two positions

Model # RD310

3-3/8"

10-3/4"

CALCULATING CUBIC FEET PER MINUTE (C.F.M.)

Gasket

Plenum

Adapter

Studs Located on Bottom of

Exhaust Plenum

Adapter Mounting

Bracket

Figure 24

CL

Summary of Contents for RDDS30V

Page 1: ...GAZ Ne pas essayer d allumer aucun appareil Ne pas toucher aucun interrupteur lectrique ne pas utiliser aucun t l phone dans votre b timent Appeler imm diatement votre fournisseur de gaz du t l phone...

Page 2: ...tion appropri e des gaz par le conduit de fum e chemin e des appaeils combustible pour viter le refoulement Suivre la directive des fabricants du mat riel chauffant et les normes de s curit tel que ce...

Page 3: ...rface and the bottom of an unprotected wood or metal cabinet or 24 inches when bottom of wood or metal cabinet is protected by not less than 1 4 of flame retardant material covered with not less than...

Page 4: ...ve the existing back brace see Figure 27 Page 18 and use floor mounted anti tip bracket see Figure 30 Page 19 NOTE Follow all measurements precisely If working with nonstandard cabinets take care to a...

Page 5: ...au de 14 0 pounces du r gulateur du r servoir de gaz du propane WARNING Do not attempt any adjustment of the pressure regulator except conversion to propane AVERTISSEMENT Ne pas entreprener aucun ajus...

Page 6: ...If local code requires separate ground separate white wire and bare gound wire connect white to white and ground bare wire separately GAS CONNECTION MODEL RDDS30V GAS CONNECTION For gas units a 1 2 N...

Page 7: ...wer Cord Receptacle Integral Blower Front Rail 2 Units using Remote Blower a Wiring the Remote Blower Wire connections between the range and remote blower shall be made as follows 1 Remove plenum cove...

Page 8: ...ust to roof angle Tape all joints to prevent air leaks NOTE The unit must be sealed between the roof or wall and the underside of the flange with roofing mastic to prevent leaks For installation on a...

Page 9: ...ng See pages 10 to 12 for specific installation steps Threaded rods included in the blower kit will be secured to the mounting nuts A or B shown in Figure 15 Further installation instructions are spec...

Page 10: ...nsure gasket between blower and plenum is compressed 1 Determine blower direction and cutout in cabinet as shown in Figs 16 17 Remove the existing 1 4 20 screws from either positions A or B and discar...

Page 11: ...plenum outlet ring Figure 14 temporarily supporting blower with wood blocks 5 Place slot end of blower mounting bracket over rear mounting rod lower nut 6 Rotate blower mounting bracket under blower...

Page 12: ...rod has one preset nut which shall be tightened against plenum 4 Place blower inlet over plenum outlet ring Figure 14 temporarily supporting blower with wood blocks 5 Place slot end of blower mounting...

Page 13: ...to standard ducts See Figure 21 Exterior ducting may be routed right left rear up rear wall above and below floor line See Figure 22 VENTILATION Figure 21 Ducting Adapters Model RD7 Model RD310 REMOT...

Page 14: ...will need to transition from other duct sizes to achieve the 10 diameter Be sure to use proper transitions from one size duct to another NOTE You need to calculate the equivalent lengths of straight d...

Page 15: ...420 C F M BLOWER DUCT SIZING Based on the blower position determine the required straight duct length and size and the number and types of elbows or transitions Calculate the total equivalent length u...

Page 16: ...16 BLOWER DUCT SIZING...

Page 17: ...Cap Round to 3 1 4 x 10 Round to 3 1 4 x 10 90 Elbow 45 Elbow 3 1 4 x 10 to 10 Dia Model 310TR10 Equiv Length 1 Ft Fitting Straight Dia Length 6 5 Ft 7 4Ft 8 3 Ft Fitting Straight Dia Length 6 1 Ft 7...

Page 18: ...shall allow the range back brace to slide under the anti tip bracket See Figure 26 c If necessary add spacer between bracket and wall to insure anti tip bracket engagement d Slide range into position...

Page 19: ...LATION Figure 29 Placement of Anti tip Bracket to Floor TopView 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 12345678901 1234...

Page 20: ...dor reserves the right to change specifications or design without notice Some models are certified for use in Canada Thermador is not responsible for products which are transported from the United Sta...

Reviews: