background image

Blower does not run. Compressor runs briefly but cycles 
on & off.

1.  Loose connection in blower circuit (Fig. 4).
2.  Obstruction prevents impeller rotation.
3.  Defective blower (Sec. 5.5).

Unit removes some water but not as much as expected.

1.  Air temperature and/or humidity have dropped.
2.  Humidity meter and/or thermometer used are out of 

calibration.

3.  Unit has entered defrost cycle (Sec. 3.3 & 5.10).
4.  Air filter dirty (Sec. 4.1).
5.  Defrost timer incorrectly set for conditions  

(Sec. 3.3 & 5.10).

6.  Defective defrost thermostat (Sec. 5.10).
7.  Low refrigerant charge (Sec. 5.4).
8.  Air leak such as loose cover.
9.  Defective compressor (Sec. 5.6).
10. Restrictive ducting (Sec. 2.4).

Pump does not pump water.

1.  Hose kinked or plugged.
2.  Pump check valve plugged (Sec. 5.11).
3.  Bad connection in pump circuit (Fig. 4).
4.  Hose disconnected internally.

Evaporator coil frosted continuously, low dehumidifying 
capacity.

1.  Defrost thermostat loose or defective  

(Sec. 3.3 & 5.10).

2.  Low refrigerant charge (Sec. 5.4).
3.  Dirty air filters or airflow restricted. (Sec. 4.1).
4.  Defrost timer set incorrectly (Sec. 3.3).

5.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, 
a new charge must be accurately weighed in. If any of 
the old charge is left in the system, it must be removed 
before weighing in the new charge. Refer to the unit 
nameplate for the correct charge weight and refrigerant 
type. Add the refrigerant through the low side service 
port (See Fig. 5).

5.5 Blower Replacement

The centrifugal blower has a PSC motor and internal 
thermal overload protection. If defective, the complete 
assembly must be replaced.
1.   Unplug the power cord.
2.   If an outlet duct is connected to the unit, remove it.
3.   Remove the cabinet side.

4.   Remove the 4 screws holding the electrical box 

located next to the blower.

5.   Disconnect the blower leads. Black from the blower 

switch, and white the run capacitor.

6.   Unbolt the blower capacitor from the blower motor 

(required for removal clearance). 

7.   Remove the nuts & bolts holding the blower outlet 

flange to the cabinet end and remove the blower.

8.   Reassembling with the new blower is the above 

procedure reversed.

5.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external 
overload, run capacitor, but no start capacitor or relay 
(see Fig. 4).

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power 
must be present to perform some tests; these tests 
should be performed by a qualified service person.

5.6A Checking Compressor Motor Circuits

Perform the following tests if the blower runs but the 
compressor does not with the humidity control ON.
1.  Turn the humidity control OFF and unplug the unit, 

remove the cabinet front (6 screws).

2.  Plug in the unit and turn the humidity control ON. Use 

a voltmeter to check for 110 to 120 volts between 
(a) the relay terminal that the black wire from the 
compressor connects to and (b) the capacitor 
terminal with the (2) white wires, (1) red wire & (1) 
brown wire connected. If voltage is present, go to 
step 3. If no voltage, the defrost thermostat, the 
relay or the condensate pump safety switch are open 
or there is a loose connection in the compressor 
circuit. Test each component for continuity; see the 
appropriate section if a defect is suspected.

3.  Turn the humidity control OFF and unplug the unit, 

then disconnect the red and yellow wires from 
compressor terminals R & S. Using an ohmmeter 
check continuity between the points listed below.

4.  Compressor terminals C and S: No continuity 

indicates an open start winding; the compressor 
must be replaced.

5.  Compressor terminals C and R: No continuity 

indicates an open run winding; the compressor must 
be replaced.

6.  Compressor terminal C and overload terminal 1: No 

continuity indicates a defective overload lead.

7.  Overload terminals 1 and 3: If there is no continuity, 

the overload may be tripped; wait 10 minutes and try 
again. If there is still no continuity, it is defective and 
must be replaced.

5

www.thermastor.com • [email protected]

Toll-Free 1-800-533-7533

www.sylvane.com 1-800-934-9194

Summary of Contents for HI-E DRY 100

Page 1: ...Free 1 800 533 7533 www thermastor com sales thermastor com Table of Contents 1 Specifications 1 2 Installation 1 2 1 Location 1 2 1A In humid area no ducting 1 2 1B In humid area duct inlet and or o...

Page 2: ...adequate air flow path must exist between the two rooms for this method to work well An additional humidity control may need to be mounted in the humid area and wired to the HI E Dry to accurately ma...

Page 3: ...y whether the unit is dehumidifying or not This function is desirable if the unit is used for air circulation or fresh air ventilation 3 3 Defrost Control Adjustment When the HI E Dry 100 is used in a...

Page 4: ...t pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates The evaporator operates in a flooded condition which means that it shou...

Page 5: ...wer motor required for removal clearance 7 Remove the nuts bolts holding the blower outlet flange to the cabinet end and remove the blower 8 Reassembling with the new blower is the above procedure rev...

Page 6: ...while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line filter driers will probably clean up the s...

Page 7: ...eplace the condensate pump 1 Unplug the unit remove the front cover 2 Disconnect the 2 hoses from the pump 3 Cut the pump lead wires near the old pump 4 Remove the 2 nuts from the unit side that hold...

Page 8: ...mostat 4021648 1 Defrost Thermostat Mounting Clip for item 12 13 4028225 1 Evaporator Coil 14 4029510 1 Filter Drier 15 4017152 1 Hose Drain 38 OD x 20 long 16 4021469 1 Humidity Controller 17 4021495...

Page 9: ...ions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot 9 www thermastor com sales thermastor com Toll Free 1 800 533 7533...

Page 10: ...10 www thermastor com sales thermastor com Toll Free 1 800 533 7533 www sylvane com 1 800 934 9194...

Page 11: ...use lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor s reasonable control Lim...

Reviews: